Development of optimized PPP insulated pipe-cable systems in the commercial voltage range. Final report
Technical Report
·
OSTI ID:10148639
- Cablec Corp., Yonkers, NY (United States)
The primary objectives of this project included the development of an alternate domestic source of Paper-Polypropylene-Paper (PPP) laminate and the development of optimized designs for PPP-insulated pipe-type cable systems in the commercial voltage range. The development of a domestic source of PPP laminate was successfully completed. This laminate was utilized throughout the program for fabrication of full-size prototype cables submitted for laboratory qualification tests. Selected cables at rated voltages of 138, 230 and 345kV have been designed, fabricated and subjected to the series of qualification tests leading to full laboratory qualification. An optimized design of 2000 kcmil, 345kV cable insulated with 600 mils of domestic PPP laminate was fabricated and successfully passed all laboratory qualification tests. This cable design was subsequently installed at Waltz Mill to undergo the series of field tests leading to full commercial qualification.
- Research Organization:
- Electric Power Research Inst., Palo Alto, CA (United States); Cablec Corp., Yonkers, NY (United States)
- Sponsoring Organization:
- Electric Power Research Inst., Palo Alto, CA (United States)
- OSTI ID:
- 10148639
- Report Number(s):
- EPRI-TR--100416; ON: UN92014733
- Country of Publication:
- United States
- Language:
- English
Similar Records
Development of optimized PPP insulated pipe-cable systems in the commercial voltage range
Development and laboratory testing of a 138-kV PPP-insulated joint for commercial application
Development of 230-kV high-pressure, gas-filled, pipe-type cable system: Model test program phase
Technical Report
·
Fri May 01 00:00:00 EDT 1992
·
OSTI ID:5174563
Development and laboratory testing of a 138-kV PPP-insulated joint for commercial application
Journal Article
·
Sat Mar 31 23:00:00 EST 1990
· IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (USA)
·
OSTI ID:6718662
Development of 230-kV high-pressure, gas-filled, pipe-type cable system: Model test program phase
Technical Report
·
Sat Sep 01 00:00:00 EDT 1990
·
OSTI ID:6559259