Integrating event detection system operation characteristics into sensor placement optimization.

Conference ·
OSTI ID:1014639
We consider the problem of placing sensors in a municipal water network when we can choose both the location of sensors and the sensitivity and specificity of the contamination warning system. Sensor stations in a municipal water distribution network continuously send sensor output information to a centralized computing facility, and event detection systems at the control center determine when to signal an anomaly worthy of response. Although most sensor placement research has assumed perfect anomaly detection, signal analysis software has parameters that control the tradeoff between false alarms and false negatives. We describe a nonlinear sensor placement formulation, which we heuristically optimize with a linear approximation that can be solved as a mixed-integer linear program. We report the results of initial experiments on a real network and discuss tradeoffs between early detection of contamination incidents, and control of false alarms.
Research Organization:
Sandia National Laboratories
Sponsoring Organization:
USDOE
DOE Contract Number:
AC04-94AL85000
OSTI ID:
1014639
Report Number(s):
SAND2010-3268C
Country of Publication:
United States
Language:
English

Similar Records

Sensor placement for municipal water networks.
Conference · Tue Nov 30 23:00:00 EST 2010 · OSTI ID:1038219

Water quality sensor placement in water networks with budget constraints.
Conference · Mon Jan 31 23:00:00 EST 2005 · OSTI ID:950963

Sensor placement in municipal water networks.
Journal Article · Wed Sep 01 00:00:00 EDT 2004 · Proposed for publication in the Journal of Water Resources Planning and Management. · OSTI ID:951710