Worker productivity and ventilation rate in a call center: Analyses of time-series data for a group of registered nurses
We investigated the relationship of ventilation rates with the performance of advice nurses working in a call center. Ventilation rates were manipulated; temperatures, humidities, and CO{sub 2} concentrations were monitored; and worker performance data, with 30-minute resolution, were collected. Multivariate linear regression was used to investigate the association of worker performance with indoor minus outdoor CO{sub 2} concentration (which increases with decreasing ventilation rate per worker) and with building ventilation rate. Results suggest that the effect of ventilation rate on worker performance in this call center was very small (probably less than 1%) or nil, over most of the range of ventilation rate (roughly 12 L s{sup -1} to 48 L s{sup -1} per person). However, there is some evidence of worker performance improvements of 2% or more when the indoor CO{sub 2} concentration exceeded the outdoor concentration by less than 75 ppm.
- Research Organization:
- Lawrence Berkeley National Lab. (LBNL), Berkeley, CA (United States)
- Sponsoring Organization:
- USDOE. Assistant Secretary for Energy Efficiency and Renewable Energy,Office of the Building Technologies Program; Center for the Built Environment. University of California Berkeley (US)
- DOE Contract Number:
- AC03-76SF00098
- OSTI ID:
- 836796
- Report Number(s):
- LBNL-53785; R&D Project: 474508; TRN: US200504%%306
- Resource Relation:
- Other Information: PBD: 1 Aug 2003
- Country of Publication:
- United States
- Language:
- English
Similar Records
Worker performance and ventilation in a call center: Analyses of work performance data for registered nurses
Worker performance and ventilation: Analyses of individual data for call-center workers