Title: Potential Cooling Energy Savings of Economizer Control and Artificial-Neural-Network-Based Air-Handling Unit Discharge Air Temperature Control for Commercial Building

Journal Article · · Buildings
 [1]; ORCiD logo [2];  [2]
  1. Oak Ridge National Lab. (ORNL), Oak Ridge, TN (United States); North Carolina State University, Raleigh, NC (United States)
  2. North Carolina State University, Raleigh, NC (United States)

Heating, ventilation, and air-conditioning (HVAC) systems play a significant role in building energy consumption, accounting for around 50% of total energy usage. As a result, it is essential to explore ways to conserve energy and improve HVAC system efficiency. One such solution is the use of economizer controls, which can reduce cooling energy consumption by using the free-cooling effect. However, there are various types of economizer controls available, and their effectiveness may vary depending on the specific climate conditions. To investigate the cooling energy-saving potential of economizer controls, this study employs a dry-bulb temperature-based economizer control approach. The dry-bulb temperature-based control strategy uses the outdoor air temperature as an indicator of whether free cooling can be used instead of mechanical cooling. This study also introduces an artificial neural network (ANN) prediction model to optimize the control of the HVAC system, which can lead to additional cooling energy savings. To develop the ANN prediction model, the EnergyPlus program is used for simulation modeling, and the Python programming language is employed for model development. The results show that implementing a temperature-based economizer control strategy can lead to a reduction of 7.6% in annual cooling energy consumption. Moreover, by employing an ANN-based optimal control of discharge air temperature in air-handling units, an additional 22.1% of cooling energy savings can be achieved. In conclusion, the findings of this study demonstrate that the implementation of economizer controls, especially the dry-bulb temperature-based approach, can be an effective strategy for reducing cooling energy consumption in HVAC systems. Additionally, using ANN prediction models to optimize HVAC system controls can further increase energy savings, resulting in improved energy efficiency and reduced operating costs.

Research Organization:
Oak Ridge National Lab. (ORNL), Oak Ridge, TN (United States)
Sponsoring Organization:
USDOE Office of Energy Efficiency and Renewable Energy (EERE)
Grant/Contract Number:
AC05-00OR22725
OSTI ID:
1972544
Journal Information:
Buildings, Vol. 13, Issue 5; ISSN 2075-5309
Publisher:
MDPICopyright Statement
Country of Publication:
United States
Language:
English

References (20)

Artificial neural network model for forecasting sub-hourly electricity usage in commercial buildings journal January 2016
Determination of free cooling potential: A case study for İstanbul, Turkey journal March 2011
A hybrid method of dynamic cooling and heating load forecasting for office buildings based on artificial intelligence and regression analysis journal September 2018
Energy Conservation Potential of Economizer Controls Using Optimal Outdoor Air Fraction Based on Field Study journal September 2020
Performance prediction of solid desiccant – Vapor compression hybrid air-conditioning system using artificial neural network journal May 2016
Modelling and analysis of air-cooled reciprocating chiller and demand energy savings using passive cooling journal June 2009
Application of artificial neural networks for optimized AHU discharge air temperature set-point and minimized cooling energy in VAV system journal May 2019
ANN based automatic slat angle control of venetian blind for minimized total load in an office building journal March 2019
A novel clustering-enhanced adaptive artificial neural network model for predicting day-ahead building cooling demand journal November 2020
The potential for office buildings with mixed-mode ventilation and low energy cooling systems in arid climates journal October 2013
Analysis of energy saving potential of air-side free cooling for data centers in worldwide climate zones journal September 2013
Modeling of a mechanical cooling system with variable cooling capacity by using artificial neural network journal September 2007
Energy analysis on VAV system with different air-side economizers in China journal August 2010
Assessment of practical applications of outdoor air economiser in Hong Kong journal August 2000
Research on short-term and ultra-short-term cooling load prediction models for office buildings journal November 2017
Detailed analysis on part load ratio characteristics and cooling energy saving of chiller staging in an office building journal May 2016
ANN-Based Prediction and Optimization of Cooling System in Hotel Rooms journal September 2015
Application of Artificial Neural Network for the Optimum Control of HVAC Systems in Double-Skinned Office Buildings journal December 2019
An energy performance study of several factors in air economizers with low-limit space humidity journal September 2013
Application of artificial neural network for predicting hourly indoor air temperature and relative humidity in modern building in humid region journal June 2016