Title: Optimal Technology Selection and Operation of Microgrids inCommercial Buildings

Conference ·
OSTI ID:928234

The deployment of small (<1-2 MW) clusters of generators,heat and electrical storage, efficiency investments, and combined heatand power (CHP) applications (particularly involving heat activatedcooling) in commercial buildings promises significant benefits but posesmany technical and financial challenges, both in system choice and itsoperation; if successful, such systems may be precursors to widespreadmicrogrid deployment. The presented optimization approach to choosingsuch systems and their operating schedules uses Berkeley Lab'sDistributed Energy Resources Customer Adoption Model [DER-CAM], extendedto incorporate electrical storage options. DER-CAM chooses annual energybill minimizing systems in a fully technology-neutral manner. Anillustrative example for a San Francisco hotel is reported. The chosensystem includes two engines and an absorption chiller, providing anestimated 11 percent cost savings and 10 percent carbon emissionreductions, under idealized circumstances.

Research Organization:
Lawrence Berkeley National Lab. (LBNL), Berkeley, CA (United States)
Sponsoring Organization:
USDOE Director, Office of Science
DOE Contract Number:
DE-AC02-05CH11231
OSTI ID:
928234
Report Number(s):
LBNL-62315; R&D Project: E584EE; BnR: YN1901000; TRN: US200815%%796
Resource Relation:
Conference: IEEE 2007 PES General Meeting, Tampa, Florida,24-28 June 2007
Country of Publication:
United States
Language:
English