Title: Response of the Los Azufres Geothermal Field to Four Years of 25 MW Wellhead Generation

Conference ·
OSTI ID:888532

Production and chemical data have been compiled and analyzed on a six-month averaged basis for the first four years of electric energy generation with five 5-MW wellhead generators at the Los Azufres geothermal field. The data were evaluated with respect to the extent of observable thermal drawdown of the reservoir from 25 MW of generation in relation to the estimated capacity of the field of several hundred megawatts of power. The analysis updates the previous one compiled after the first two years of continuous production, at which time the results indicated that differences in reservoir temperature estimated from geochemical thermometers and wellhead production data were not statistically significant based on the number of data and the standard deviations. Analysis of the data after four years of operation were made for the larger number of data and smaller standard deviations. The results review the adequacy of the sampling frequency and the reliability of the measurements from statistical t-Test of the means of the first and second two-year periods. 3 figs., 5 tabs., 20 refs.

Research Organization:
Stanford Geothermal Program, Stanford University, Stanford, CA; Los Azufres Geothermal Field, Comision Federal de Electricidad, Ciudad Hidalgo, Michoacan
Sponsoring Organization:
USDOE
DOE Contract Number:
AT03-80SF11459; AS07-84ID12529
OSTI ID:
888532
Report Number(s):
SGP-TR-109-26
Resource Relation:
Conference: Proceedings, Twelfth Workshop on Geothermal Reservoir Engineering, Stanford University, Stanford, Calif., January 20-22, 1987
Country of Publication:
United States
Language:
English