skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: Report on Analyses of WAC Samples of Evaporator Overheads - 2004

Technical Report ·
DOI:https://doi.org/10.2172/835582· OSTI ID:835582

All water received into ETF requires characterization versus the defined Waste Acceptance Criteria. Currently much of the water received by ETF comes from the F and H Evaporator Overheads. Concentration, Storage and Transfer Engineering issued a modified list of species to be determined. In March of 2004, the Tank Farm submitted annual samples from 2F, 2H and 3H Evaporator Overhead streams for characterization to verify compliance with the Effluent Treatment Facility (ETF) Waste Acceptance Criteria (WAC) and to look for organic species. With the exception of high silicon in the 2H and slightly high tritium in 2F evaporator overheads, all the overheads samples were found to be in compliance with the Effluent Treatment Facility WAC. The silicon concentration in the 2H-evaporator overhead, at 44 mg/L, was above the ETF WAC limit of 5 mg/L and tritium at 2.11E+05 dpm/mL in 2F overhead sample was above the ETF WAC limit of 1.2E+05 dpm/mL.

Research Organization:
Savannah River Site (SRS), Aiken, SC (United States)
Sponsoring Organization:
US Department of Energy (US)
DOE Contract Number:
AC09-96SR18500
OSTI ID:
835582
Report Number(s):
WSRC-TR-2004-00281; TRN: US0500087
Resource Relation:
Other Information: PBD: 16 Aug 2004
Country of Publication:
United States
Language:
English