Criteria for calculating the efficiency of deep-pleated HEPA filters with aluminum separators during and after design basis accidents
- Lawrence Livermore National Lab., CA (United States)
- Harvard School of Public Health, Boston, MA (United States)
- Anderson (W.L.), LaPlata, MD (United States)
- Gilbert (H.), McLean, VA (United States)
- Jacox (J.W.), Columbus, OH (United States)
The authors have reviewed the literature on the performance of high efficiency particulate air (HEPA) filters under normal and abnormal conditions to establish criteria for calculating the efficiency of HEPA filters in a DOE nonreactor nuclear facility during and after a Design Basis Accident (DBA). This study is only applicable to the standard deep-pleated HEPA filter with aluminum separators as specified in ASME N509. The literature review included the performance of new filters and parameters that may cause deterioration in the filter performance such as filter age, radiation, corrosive chemicals, seismic and rough handling, high temperature, moisture, particle clogging, high air flow and pressure pulses. The deterioration of the filter efficiency depends on the exposure parameters; in severe exposure conditions the filter will be structurally damaged and have a residual efficiency of 0%. Despite the many studies on HEPA filter performance under adverse conditions, there are large gaps and limitations in the data that introduce significant error in the estimates of HEPA filter efficiencies under DBA conditions. Because of this limitation, conservative values of filter efficiency were chosen when there was insufficient data.
- Research Organization:
- Lawrence Livermore National Lab. (LLNL), Livermore, CA (United States)
- Sponsoring Organization:
- USDOE, Washington, DC (United States)
- DOE Contract Number:
- W-7405-ENG-48
- OSTI ID:
- 71317
- Report Number(s):
- UCRL-JC-119798; CONF-940738-12; ON: DE95011438; TRN: 95:015301
- Resource Relation:
- Conference: 23. DOE/NRC nuclear air cleaning and treatment conference, Buffalo, NY (United States), 25-28 Jul 1994; Other Information: PBD: Feb 1995
- Country of Publication:
- United States
- Language:
- English
Similar Records
Criteria for calculating the efficiency of HEPA filters during and after design basis accidents
Results from Evaluation of Representative ASME AG-1 Section FK Radial Flow Dimple Pleated HEPA Filters Under Elevated Conditions - 12002