Title: Functional design criteria for interim stabilization safety class 1 trip circuit

Technical Report ·
DOI:https://doi.org/10.2172/657370· OSTI ID:657370

This Functional Design Criteria document outlines the basic requirements for the Safety Class 1 Trip Circuit. The objective of the Safety Class 1 Trip Circuit is to isolate the power circuitry to the Class 1 Division 2, Group B or lesser grade electrically fed loads located in the pump pit. The electrically fed load circuits need to have power isolated to them upon receipt of the following conditions, loss of flammable gases being released (above a predetermined threshold), and seismic(greater than 0.12g acceleration) activity. The two circuits requiring power isolation are the pump and heat trace power circuits. The Safety Class 1 Trip Circuit will be used to support salt well pumping in SST`s containing potentially flammable gas-bearing / gas-producing radioactive waste.

Research Organization:
Westinghouse Hanford Co., Richland, WA (United States)
Sponsoring Organization:
USDOE Office of Environmental Restoration and Waste Management, Washington, DC (United States)
DOE Contract Number:
AC06-96RL13200
OSTI ID:
657370
Report Number(s):
WHC-SD-WM-FDC-053; ON: DE98054213; BR: EW3120071; TRN: 96000495
Resource Relation:
Other Information: PBD: 10 Jun 1996
Country of Publication:
United States
Language:
English