Title: Case study: Use of isothiazolinone and nitro-morpholine biocides to control microbial contamination in diesel and gasoline storage and distribution systems

Conference ·
OSTI ID:45053

Responding to feed-back from its retail outlet network, a major, vertically integrated petroleum company undertook to diagnose and remediate diesel and gasoline performance problems. Analysis of samples from tanks at refinery, distribution terminal and retail outlet sites established that uncontrolled microbial contamination was rampant throughout the distribution system. The company then developed and instituted a two-phase action plan. During Phase I, all tanks received corrective (shock) biocide treatment preceding mechanical tank cleaning and fuel polishing. An ongoing Phase II program currently includes routine sampling and analysis combined with periodic preventive biocide treatment. This paper describes the initial problem diagnosis, corrective action plan and preventive program; recommending the Phase II program as a model for all companies involved with refining, distribution or retailing gasoline.

Research Organization:
USDOE Assistant Secretary for Fossil Energy, Washington, DC (United States). Office of Technical Management
OSTI ID:
45053
Report Number(s):
CONF-941022-Vol.1; ON: DE95008873; TRN: 95:003336-0009
Resource Relation:
Conference: 5. international conference on stability and handling of liquid fuels, Rotterdam (Netherlands), 3-7 Oct 1994; Other Information: PBD: 1995; Related Information: Is Part Of Proceedings of the 5th international conference on stability and handling of liquid fuels. Volume 1; Giles, H.N. [ed.]; PB: 431 p.
Country of Publication:
United States