skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: Prototype energy models for data centers

Journal Article · · Energy and Buildings
 [1];  [1];  [1];  [1]
  1. Lawrence Berkeley National Lab. (LBNL), Berkeley, CA (United States)

Data centers in the United States consume about two percent of the nation’s electricity. Because heat gains from IT equipment drive cooling demand, data centers offer unique opportunities for energy savings. However, no prototype energy model for data centers is available in the suite of existing U.S. Department of Energy’s Commercial Prototype Building Models. Here we present the development of two new data center prototype models and their implementation in OpenStudio and EnergyPlus. The small-size data center model represents a computer room in a building served by computer room air conditioners (CRACs); while the large-sized model represents stand-alone data centers served by computer room air handlers (CRAHs) with a central chiller plant. For each data center model, two levels of IT equipment (ITE) load density were considered, to cover the wide range of IT power density of data centers: 40 and 100 W/ft2 (430 and 1076 W/m2) for the computer room, and 100 and 500 W/ft2 (1076 and 5382 W/m2) for the stand-alone data center. All other assumptions, such as building envelope, lighting, HVAC efficiencies and schedules, were based on the minimal requirements of ASHRAE Standard 90.1 at various vintages. We introduced a novel concept of supply and return air approach temperatures to capture the essential effects of non-uniform airflow and temperature distribution in data centers. The approach temperatures were pre-computed by computational fluid dynamics (CFD) simulations for various configurations of ITE loads and airflow containment management in data centers. A new feature was developed in EnergyPlus to implement the approach temperature method. A case study was conducted to demonstrate the use of the data center models. The two data center models cover all U.S. climate zones and can be used to evaluate energy saving measures for data centers, as well as to support development of data center energy efficiency codes and standards.

Research Organization:
Lawrence Berkeley National Lab. (LBNL), Berkeley, CA (United States)
Sponsoring Organization:
USDOE Office of Energy Efficiency and Renewable Energy (EERE), Energy Efficiency Office. Building Technologies Office
Grant/Contract Number:
AC02-05CH11231
OSTI ID:
1769331
Alternate ID(s):
OSTI ID: 1900040
Journal Information:
Energy and Buildings, Vol. 231; ISSN 0378-7788
Publisher:
ElsevierCopyright Statement
Country of Publication:
United States
Language:
English

References (26)

Coupled TRNSYS-CFD simulations evaluating the performance of PCM plate heat exchangers in an airport terminal building displacement conditioning system journal July 2013
Coupled EnergyPlus and computational fluid dynamics simulation for natural ventilation journal October 2013
Experimental and numerical investigation of airflow and contaminant transport in an airliner cabin mockup journal January 2009
Fundamental study of coupling methods between energy simulation and CFD journal January 2018
A review on airflow management in data centers journal April 2019
Analysis of energy saving potential of air-side free cooling for data centers in worldwide climate zones journal September 2013
Coupled simulations for naturally ventilated residential buildings journal May 2008
A thermal environmental analysis method for data centers journal July 2013
Simplified server model to simulate data center cooling energy consumption journal January 2015
Evaluation of air distribution system's airflow performance for cooling energy savings in high-density data centers journal January 2014
State of the art in building modelling and energy performances prediction: A review journal July 2013
Performance of coupled building energy and CFD simulations journal April 2005
There's a measure for that! journal April 2016
A review of power consumption models of servers in data centers journal May 2020
Achieving the goal: results from the Fistula First Breakthrough Initiative journal January 2011
Energy, environmental and economical saving potential of data centers with various economizers across Australia journal December 2016
Measurements and predictions of the air distribution systems in high compute density (Internet) data centers journal October 2009
Application of integrating multi-zone model with CFD simulation to natural ventilation prediction journal October 2005
Physical Models in Data Center Airflow Simulations conference May 2008
A review on evaluation metrics of thermal performance in data centers journal June 2020
EnergyPlus: creating a new-generation building energy simulation program journal April 2001
Data Center Energy Consumption Modeling: A Survey journal April 2016
A methodology to create prototypical building energy models for existing buildings: A case study on U.S. religious worship buildings journal July 2019
Energy saving potential of various air-side economizers in a modular data center journal January 2015
A Real-Time Data Center Airflow and Energy Assessment Tool
  • Zhang, Xuanhang Simon; VanGilder, James W.; Healey, Christopher M.
  • ASME 2009 InterPACK Conference collocated with the ASME 2009 Summer Heat Transfer Conference and the ASME 2009 3rd International Conference on Energy Sustainability, ASME 2009 InterPACK Conference, Volume 2 https://doi.org/10.1115/InterPACK2009-89175
conference December 2010
Estimating the maximum energy-saving potential based on IT load and IT load shifting journal November 2017