Title: Adaptive Environmentally Contained Power and Cooling IT Infrastructure for the Data Center

Technical Report ·
DOI:https://doi.org/10.2172/1044592· OSTI ID:1044592

The objectives of this program were to research and develop a fully enclosed Information Technology (IT) rack system for 100 kilowatts (KW) of IT load that provides its own internal power and cooling with High Voltage Alternating Current (HVAC defined as 480 volt) and chilled water as the primary inputs into the system and accepts alternative energy power sources such as wind and solar. For maximum efficiency, internal power to the IT equipment uses distributed High Voltage Direct Current power (HVDC defined as 360-380 volt) from the power source to the IT loads. The management scheme aggressively controls energy use to insure the best utilization of available power and cooling resources. The solution incorporates internal active management controls that not only optimizes the system environment for the given dynamic IT loads and changing system conditions, but also interfaces with data center Building Management Systems (BMS) to provide a complete end-to-end view of power and cooling chain. This technology achieves the goal of a Power Usage Effectiveness (PUE) of 1.25, resulting in a 38% reduction in the total amount of energy needed to support a 100KW IT load compared to current data center designs.

Research Organization:
Hewlett-Packard Company, Houston, TX; Eaton Corporation, Raleigh, NC
Sponsoring Organization:
USDOE Office of Energy Efficiency and Renewable Energy (EERE)
DOE Contract Number:
EE0002893
OSTI ID:
1044592
Report Number(s):
DOE/EE0002893-1; TRN: US201214%%697
Country of Publication:
United States
Language:
English