Title: Wildland Fire Induced Heating of Dome 375 Perma-Con®

Technical Report ·
DOI:https://doi.org/10.2172/1304738· OSTI ID:1304738
 [1]
  1. Los Alamos National Lab. (LANL), Los Alamos, NM (United States)

AET-1 was tasked by ADEM with determining the temperature rise in the drum contents of drums stored in the Dome 375 Perma-Con® at TA-54 given a wildland fire. The wildland fire causes radiative and convective heating on the Perma-Con® exterior. The wildland fire time histories for the radiative and convective heating environment were provided to AET-1 by EES-16. If the calculated temperature rise results in a drum content temperature over 40 °C, then ADEM desires a design solution to ensure the peak temperature remains below 40 °C. An axi-symmetric FE simulation was completed to determine the peak temperature of the contents of a drum stored in the Dome 375 Perma-Con® during a wildland fire event. Three wildland fire time histories for the radiative and convective heat transfer were provided by EES-16 and were inputs for the FE simulation. The maximum drum content temperature reached was found to be 110 °C while using inputs from the SiteG_2ms_4ign_wind_from_west.xlsx time history input and not including the SWB in the model. Including the SWB in the results in a peak drum content temperature of 61 °C for the SiteG_2ms_4ign_wind_from_west.xlsx inputs. EES-16 decided that by using fuel mitigation efforts, such as mowing the grass and shrubs near the Perma-Con® they could reduce the shrub/grass fuel loading near the Perma-Con® from 1.46 kg/m2 to 0.146 kg/m2 and by using a less conservative fuel loading for the debris field inside the Dome 375 perimeter, reducing it from 0.58 kg/m2 to 0.058 kg/m2 in their model. They also greatly increased the resolution of their radiation model and increased the accuracy of their model’s required convergence value. Using this refined input the maximum drum content temperature was found to be 28 °C with no SWB present in the model. Additionally, this refined input model was modified to include worst case emissivity values for the concrete, drum and Perma-Con® interior, along with adding a 91 second long residual radiative heat flux of 2,000 W/m2 to the end of the refined wildland fire input. For this case the maximum drum content temperature was found to be 32 °C. For Rev. 2 of this calculation and additional simulation was run that included a cable fire heat flux on the exterior of the Perma-Con® that was calculated by FP-DO. Including the cable fire heat flux in the model without the SWB resulted in a peak drum content temperature over time of 43 °C. Including the SWB in the simulation with the cable fire heat flux resulted in a peak drum content temperature over time of 35 °C.

Research Organization:
Los Alamos National Laboratory (LANL), Los Alamos, NM (United States)
Sponsoring Organization:
USDOE Office of Environmental Management (EM)
DOE Contract Number:
AC52-06NA25396
OSTI ID:
1304738
Report Number(s):
LA-UR-16-26130
Country of Publication:
United States
Language:
English