Title: Field Test of Boiler Primary Loop Temperature Controller

Technical Report ·
DOI:https://doi.org/10.2172/1220341· OSTI ID:1220341
 [1];  [1];  [1];  [1]
  1. Partnership for Advanced Residential Retrofit, Des Plaines, IL (United States)

Beyond these initial system efficiency upgrades are an emerging class of Advanced Load Monitoring (ALM) aftermarket controllers that dynamically respond to the boiler load, with claims of 10% to 30% of fuel savings over a heating season. For hydronic boilers specifically, these devices perform load monitoring, with continuous measurement of supply and, in some cases, return water temperatures. Energy savings from these ALM controllers are derived from dynamic management of the boiler differential, where a microprocessor with memory of past boiler cycles prevents the boiler from firing for a period of time, to limit cycling losses and inefficient operation during perceived low load conditions. These differ from OTR controllers, which vary boiler setpoint temperatures with ambient conditions while maintaining a fixed differential.

Research Organization:
Partnership for Advanced Residential Retrofit, Des Plaines, IL (United States)
Sponsoring Organization:
USDOE Office of Energy Efficiency and Renewable Energy (EERE), Energy Efficiency Office. Building Technologies Office
DOE Contract Number:
AC36-08GO28308
OSTI ID:
1220341
Report Number(s):
DOE/GO-102014-4457; 6932
Country of Publication:
United States
Language:
English