Compressor Calorimeter Test of R-404A Alternatives ARM-31a, D2Y-65, L-40, and R32 + R-134a Mixture using a Scroll Compressor
Abstract
As a contribution to the AHRI Low-GWP Alternative Refrigerants Evaluation Program (AREP), this study compares the performance of four lower-GWP alternative refrigerants, ARM-31a, D2Y-65, L-40, and R-32 + R-134a mixture, to that of refrigerant R-404A (baseline) in a scroll compressor designed for medium temperature refrigeration applications. These comparisons were carried out via compressor calorimeter tests performed on a compressor designed for refrigerant R-404A and having a nominal rated capacity of 23,500 Btu/hr. Tests were conducted over a suction dew point temperature range of -10 F to 35 F in 5 F increments and a discharge dew point temperature range of 70 F to 140 F in 10 F increments. All the tests were performed with 20 F superheat, 40 F superheat, and 65 F suction temperature. A liquid subcooling level of 10 F to 15 F was maintained for all the test conditions. However, the cooling capacities reported in this study are normalized for 0 F subcooling. The tests showed that the compressor energy efficiency ratio (EER) and cooling capacity with all four alternative refrigerants tested are higher at higher saturation suction and saturation discharge temperature and lower at lower saturation suction and saturation discharge temperature, compared to that ofmore »
- Authors:
-
- ORNL
- Publication Date:
- Research Org.:
- Oak Ridge National Lab. (ORNL), Oak Ridge, TN (United States). Building Technologies Research and Integration Center (BTRIC)
- Sponsoring Org.:
- USDOE Office of Energy Efficiency and Renewable Energy (EERE)
- OSTI Identifier:
- 1089777
- Report Number(s):
- ORNL/TM-2013/156
BT0400000; CEBT002
- DOE Contract Number:
- DE-AC05-00OR22725
- Resource Type:
- Technical Report
- Country of Publication:
- United States
- Language:
- English
- Subject:
- Alternative Refrigerants; Compressor; Calorimeter; Low GWP
Citation Formats
Shrestha, Som S, Sharma, Vishaldeep, and Abdelaziz, Omar. Compressor Calorimeter Test of R-404A Alternatives ARM-31a, D2Y-65, L-40, and R32 + R-134a Mixture using a Scroll Compressor. United States: N. p., 2013.
Web. doi:10.2172/1089777.
Shrestha, Som S, Sharma, Vishaldeep, & Abdelaziz, Omar. Compressor Calorimeter Test of R-404A Alternatives ARM-31a, D2Y-65, L-40, and R32 + R-134a Mixture using a Scroll Compressor. United States. https://doi.org/10.2172/1089777
Shrestha, Som S, Sharma, Vishaldeep, and Abdelaziz, Omar. 2013.
"Compressor Calorimeter Test of R-404A Alternatives ARM-31a, D2Y-65, L-40, and R32 + R-134a Mixture using a Scroll Compressor". United States. https://doi.org/10.2172/1089777. https://www.osti.gov/servlets/purl/1089777.
@article{osti_1089777,
title = {Compressor Calorimeter Test of R-404A Alternatives ARM-31a, D2Y-65, L-40, and R32 + R-134a Mixture using a Scroll Compressor},
author = {Shrestha, Som S and Sharma, Vishaldeep and Abdelaziz, Omar},
abstractNote = {As a contribution to the AHRI Low-GWP Alternative Refrigerants Evaluation Program (AREP), this study compares the performance of four lower-GWP alternative refrigerants, ARM-31a, D2Y-65, L-40, and R-32 + R-134a mixture, to that of refrigerant R-404A (baseline) in a scroll compressor designed for medium temperature refrigeration applications. These comparisons were carried out via compressor calorimeter tests performed on a compressor designed for refrigerant R-404A and having a nominal rated capacity of 23,500 Btu/hr. Tests were conducted over a suction dew point temperature range of -10 F to 35 F in 5 F increments and a discharge dew point temperature range of 70 F to 140 F in 10 F increments. All the tests were performed with 20 F superheat, 40 F superheat, and 65 F suction temperature. A liquid subcooling level of 10 F to 15 F was maintained for all the test conditions. However, the cooling capacities reported in this study are normalized for 0 F subcooling. The tests showed that the compressor energy efficiency ratio (EER) and cooling capacity with all four alternative refrigerants tested are higher at higher saturation suction and saturation discharge temperature and lower at lower saturation suction and saturation discharge temperature, compared to that of R-404A. Discharge temperatures of all the alternative refrigerants were higher than that of R-404A at all test conditions.},
doi = {10.2172/1089777},
url = {https://www.osti.gov/biblio/1089777},
journal = {},
number = ,
volume = ,
place = {United States},
year = {Thu Aug 01 00:00:00 EDT 2013},
month = {Thu Aug 01 00:00:00 EDT 2013}
}