Title: Effect of LOCA simulation procedures on cross-linked polyolefin cable's performance

Technical Report ·
OSTI ID:6834373

Electrical and mechanical properties of three commercial cross-linked polyolefin (XLPO) materials, typically used as electrical cable insulation, have been monitored during these simulations of nuclear power plant aging and accident stresses. For one XLPO cable accelerated thermal aging is performed, then the samples are irradiated to the combined aging and LOCA total dose. Finally, a steam exposure is applied. For a second and third set of XLPO cables simultaneous applications of elevated temperature and radiation stresses are used to preaccident age specimens. These aging exposures are followed by simultaneous and steam exposures to simulate a LOCA environment. The measurement parameters during these tests included: dc insulation resistance, ac leakage current, ultimate tensile strength, ultimate tensile elongation, percentage dimensional changes, and percentage moisture absorption. Test results for three XLPO materials are presented.

Research Organization:
Sandia National Labs., Albuquerque, NM (USA)
DOE Contract Number:
AC04-76DP00789
OSTI ID:
6834373
Report Number(s):
NUREG/CR-3588; SAND-83-2406; ON: DE84013527
Resource Relation:
Other Information: Portions are illegible in microfiche products
Country of Publication:
United States
Language:
English