Title: Health-hazard evaluation report HETA 89-065-2119, One Government Center, Toledo, Ohio

Technical Report ·
OSTI ID:6001837

In response to a request from the Ohio Department of Health, an investigation was undertaken of possible hazardous working conditions at One Government Center, a modern 22 story municipal office building located in downtown Toledo, Ohio. Employees reported fatigue, nausea, headache, and other effects perhaps linked to poor indoor air quality. The building housed offices for the city of Toledo, the county and the state of Ohio. Questionnaires were administered to workers, and air quality measurements were made on floors 15 through 22. For the most part the concentration of carbon-dioxide (124389) was below the acceptable limit (1000 parts per million) with two exceptions which probably reflected a higher occupancy level and more extensive use of office partitions. Temperature and humidity levels measured were all within the acceptable limits. Respirable particulate levels in a smoking lounge located on the seventeenth floor were 454 micrograms/cubic meter and exceeded the recommended limit of 150 micrograms/cubic meter. The authors conclude that the indoor air quality parameters were within acceptable limits in most of the areas. The authors recommend that the existing smoking policy should be modified, and that the number of employees in specific areas be reduced or the ventilation in these same areas should be increased.

Research Organization:
National Inst. for Occupational Safety and Health, Cincinnati, OH (United States)
OSTI ID:
6001837
Report Number(s):
PB-92-109222/XAB; HETA-89-065-2119
Country of Publication:
United States
Language:
English