Title: AC fog withstand test on contaminated insulators by steam fog

Journal Article · · IEEE Trans. Power Appar. Syst.; (United States)

This paper describes the results of an investigation into how steam fog parameters affect the withstand voltage of artificially contaminated insulators by the fog withstand method. Established the correlation between the steam flow rate and liquid water content of the fog. The fog withstand voltage showed a lower value with little dispersion at about 3 to 10 g/m/sup 3/ of the maximum liquid water content. The minimum fog withstand voltage agreed well with the minimum flashover voltage obtained under natural conditions. The authors suggest that, for the fog withstand test using steam fog, the ideal fog condition would be about 3 to 7 g/m/sup 3/ of the maximum liquid water content of the fog.

Research Organization:
Central Research Inst. of Electric Power Industry, Tokyo, Japan
OSTI ID:
5977578
Journal Information:
IEEE Trans. Power Appar. Syst.; (United States), Vol. PAS-101:11
Country of Publication:
United States
Language:
English

Similar Records

Influence of fog parameters on withstand voltage of contaminated insulators
Journal Article · Tue Mar 01 00:00:00 EST 1983 · IEEE Trans. Power Appar. Syst.; (United States) · OSTI ID:5977578

AC flashover performance of insulators covered with artificial ice
Journal Article · Sat Apr 01 00:00:00 EST 1995 · IEEE Transactions on Power Delivery · OSTI ID:5977578

The AC clean-fog test for contaminated insulators
Journal Article · Tue Mar 01 00:00:00 EST 1983 · IEEE Trans. Power Appar. Syst.; (United States) · OSTI ID:5977578