skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: N Reactor filter system fission-product retention assessment

Technical Report ·
OSTI ID:5684752

Data for the N Reactor High-Efficiency Particulate Air (HEPA) filter and charcoal filter systems have been evaluated to determine appropriate filter efficiencies for elemental iodine, methyl iodide, hydrogen iodide, and particulates. The data supports the following filter efficiencies: particulates - 99.95%, elemental iodine - 99%, methyl iodide - 70%, and hydrogen iodide - 99%. The HEPA filter and charcoal filter system, loading capacities have been determined for both radionuclide and non-radioactive aerosols. The results demonstrated that the capacity of the N Reactor confinement filtration system is more than adequate to retain both radionuclide and non-radioactive aerosols postulated to be released during accident situations without overloading. In addition, potential filter failure due to unacceptable heat loads from collected radionuclides was evaluated. The results show that with an acceptable air flow through the filter system (greater than 850 ft/sup 3//min), the heat load on the filters from deposited radionuclides will not lead to filter failure. 30 refs., 8 figs., 13 tabs.

Research Organization:
Westinghouse Hanford Co., Richland, WA (USA)
DOE Contract Number:
AC06-87RL10930
OSTI ID:
5684752
Report Number(s):
WHC-SP-0233; ON: DE89015991
Resource Relation:
Other Information: Portions of this document are illegible in microfiche products
Country of Publication:
United States
Language:
English