Title: Varistor-particle lightning arrestor connector performance under simulated extreme lightning currents

Conference ·
OSTI ID:5633624

Varistor-particle lightning arrestor connectors have been tested under simulated lightning currents of peak amplitude up to 185 kA. Each connector was attached to a circuit of representative interest, in which currents were measured at various points. These currents were reproduced in post-test circuit modeling, during which voltages were determined throughout the circuit and response sensitivity to statistical variations in post-breakdown contact-arc voltage was demonstrated. In all cases, resultant downstream circuit voltages were well below the 1500-V criterion. 6 refs., 10 figs., 3 tabs.

Research Organization:
Sandia National Labs., Albuquerque, NM (USA)
DOE Contract Number:
AC04-76DP00789
OSTI ID:
5633624
Report Number(s):
SAND-88-3470C; CONF-8909124-2; ON: DE89012663
Resource Relation:
Conference: International conference on lightning and static electricity, Bath, UK, 26-28 Sep 1989; Other Information: Portions of this document are illegible in microfiche products