skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: Leak-rate qualification of the FFTF control area

Conference ·
OSTI ID:5564326

Positive experience with the Fast Flux Test Facility (FFTF) Control Area boundary has demonstrated that strigent requirements for reactor control room leak-tightness can be met and maintained. Guidance contained in 10CFR50, Appendix A, Criteria 4 and 19, and Regulatory Guides 1.78 and 1.95 provided criteria for control room habitability, to provide safe, central control of the FFTF plant under normal and accident conditions. A leak rate criterion of 178 scfm for the approximate 53,000 cu. ft. Volume of the Control Area was established for the limiting condition of airborne sodium oxide aerosols from a postulated fire in one of the three secondary sodium loops. Numerous tests utilizing a variety of leak identification techniques were conducted.

Research Organization:
Hanford Engineering Development Lab., Richland, WA (USA)
DOE Contract Number:
AC06-76FF02170
OSTI ID:
5564326
Report Number(s):
HEDL-SA-2829; CONF-830695-8; ON: DE84001481
Resource Relation:
Conference: Health Physics Society annual meeting, Baltimore, MD, USA, 19 Jun 1983; Other Information: Portions are illegible in microfiche products
Country of Publication:
United States
Language:
English