skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: Dynamic model of a three-phase power transformer

Journal Article · · IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States)
DOI:https://doi.org/10.1109/61.248289· OSTI ID:5385585
; ;  [1]
  1. Univ. of Maribor (Slovenia). Faculty of Technical Sciences

An adequate mathematical model of a three-phase power transformer is one of the important elements in the programs for the computer analysis of power system transients. Featured in this paper is the simulation model of a three-phase, three-limb core-type power transformer. Non-linear effects of saturation, hysteresis and eddy currents are considered. Two ways of creating major and minor hysteresis loops are presented. The transformer model, described by a system of time dependent differential equations, is solved by an efficient numerical algorithm. The behavior of the transformer model during switching-in and fault transients, as well as other types of transients, has been tested. The computed transient waveforms are compared with the measured ones of there exists very close agreement between them.

OSTI ID:
5385585
Journal Information:
IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States), Vol. 8:4; ISSN 0885-8977
Country of Publication:
United States
Language:
English