Title: Development of desiccant based air conditioning for hotels and motels. Final report, phase 1

Technical Report ·
OSTI ID:48160

This report contains final reports from two phases of field tests: Phase I at the Marriott Courtyard in West Palm Beach, completed in October 1991, and Phase II at the Walt Disney World Swan Hotel in Orlando, completed in August 1993. The goal was to measure the performance and reliability of the desiccant units. The successfull program proved the value of the gas-fired desiccant technology to the hospitality industry. The desiccant units reduced moisture by 15 to 20% relative humidity. Measurements of temperature, humidity, and wallboard moisture content showed a dramatic reduction in the humidity levels experienced prior to installation of the units and in the control areas without desiccants. Moisture damage was kept in check and remodelling due to it was eliminated.