skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: Testing of Minuteman launch facility flooded lead acid batteries for service life projection

Conference ·
OSTI ID:382666
;  [1]
  1. TRW Strategic Systems Div., Ogden, UT (United States)

Capacity performance tests were completed on 47 flooded lead-calcium batteries ranging from 5- to 23-years-old. These batteries had been maintained in the Minuteman missile silos on float charge over the majority of their life to provide emergency or secondary power. Capacity results showed no capacity degradation in the oldest batteries and cell dissections revealed only minor deterioration of the lead calcium grids. However, an increase in the cell float voltage range was observed in the 23-year-old batteries. Although signs of deterioration have begun, the solid capacity results indicate additional service life is still available. Additional data is also presented from on-going cycle tests being performed on a 5- and 21-year-old battery which supports the performance capability remaining in these aged batteries.

OSTI ID:
382666
Report Number(s):
CONF-960112-; ISBN 0-7803-2994-5; TRN: IM9645%%217
Resource Relation:
Conference: 11. annual battery conference on applications and advances, Long Beach, CA (United States), 9-12 Jan 1996; Other Information: PBD: 1996; Related Information: Is Part Of The eleventh annual battery conference on applications and advances: Proceedings; PB: 355 p.
Country of Publication:
United States
Language:
English

Similar Records

Small ICBM area narrowing report. Volume 2. Hard mobile launcher at minuteman facilities basing mode
Technical Report · Wed Jan 01 00:00:00 EST 1986 · OSTI ID:382666

Test series 1: seismic-fragility tests of naturally-aged Class 1E Gould NCX-2250 battery cells
Technical Report · Sat Sep 01 00:00:00 EDT 1984 · OSTI ID:382666

Strategic forces
Technical Report · Mon Oct 01 00:00:00 EDT 1990 · OSTI ID:382666