Title: Construction and measurements of an improved vacuum-swing-adsorption radon-mitigation system

In order to reduce backgrounds from radon-daughter plate-out onto detector surfaces, an ultra-low-radon cleanroom is being commissioned at the South Dakota School of Mines and Technology. An improved vacuum-swing-adsorption radon mitigation system and cleanroom build upon a previous design implemented at Syracuse University that achieved radon levels of ∼0.2 Bq m{sup −3}. This improved system will employ a better pump and larger carbon beds feeding a redesigned cleanroom with an internal HVAC unit and aged water for humidification. With the rebuilt (original) radon mitigation system, the new low-radon cleanroom has already achieved a > 300× reduction from an input activity of 58.6 ± 0.7 Bq m{sup −3} to a cleanroom activity of 0.13 ± 0.06 Bq m{sup −3}.
Authors:
; ; ; ; ; ; ;  [1]
  1. Department of Physics, South Dakota School of Mines & Technology, Rapid City, SD 57701 (United States)
Publication Date:
OSTI Identifier:
22488741
Resource Type:
Journal Article
Resource Relation:
Journal Name: AIP Conference Proceedings; Journal Volume: 1672; Journal Issue: 1; Conference: LRT 2015: 5. international workshop in low radioactivity techniques, Seattle, WA (United States), 18-20 Mar 2015; Other Information: (c) 2015 AIP Publishing LLC; Country of input: International Atomic Energy Agency (IAEA)