Title: Verification of voltage/frequency requirement for emergency diesel generator in nuclear power plant using dynamic modeling

One major cause of the plant shutdown is the loss of electrical power. The study is to comprehend the coping action against station blackout including emergency diesel generator, sequential loading of safety system and to ensure that the emergency diesel generator should meet requirements, especially voltage and frequency criteria using modeling tool. This paper also considered the change of the sequencing time and load capacity only for finding electrical design margin. However, the revision of load list must be verified with safety analysis. From this study, it is discovered that new load calculation is a key factor in EDG localization and in-house capability increase.
Authors:
;  [1]
  1. KEPCO International Nuclear Graduate School, 1456-1 Shinam-ri, Seosaeng-myeon, Ulju-gun, Ulsan, 689-882 (Korea, Republic of)
Publication Date:
OSTI Identifier:
22266067
Resource Type:
Journal Article
Resource Relation:
Journal Name: AIP Conference Proceedings; Journal Volume: 1584; Journal Issue: 1; Conference: iNuSTEC2013: International nuclear science, technology and engineering conference 2013, Kuala Lumpur (Malaysia), 30 Sep - 2 Oct 2013; Other Information: (c) 2014 AIP Publishing LLC; Country of input: International Atomic Energy Agency (IAEA)
Country of Publication:
United States
Language:
English
Subject:
46 INSTRUMENTATION RELATED TO NUCLEAR SCIENCE AND TECHNOLOGY; 71 CLASSICAL AND QUANTUM MECHANICS, GENERAL PHYSICS; ELECTRIC POTENTIAL; NUCLEAR POWER PLANTS; SAFETY ANALYSIS; SIMULATION