Title: Applications of Living Fire PRA models to Fire Protection Significance Determination Process in Taiwan

Conference ·
OSTI ID:21160571
; ; ;  [1];  [2]
  1. Institute of Nuclear Energy Research, P. O. Box 3-3, Lung-Tan, Tao-Yuan Taiwan (China)
  2. ABSG Consulting Inc., 300 Commerce Drive, Suite 200, Irvine, CA 92602 (United States)

The living fire probabilistic risk assessment (PRA) models for all three operating nuclear power plants (NPPs) in Taiwan had been established in December 2000. In that study, a scenario-based PRA approach was adopted to systematically evaluate the fire and smoke hazards and associated risks. Using these fire PRA models developed, a risk-informed application project had also been completed in December 2002 for the evaluation of cable-tray fire-barrier wrapping exemption. This paper presents a new application of the fire PRA models to fire protection issues using the fire protection significance determination process (FP SDP). The fire protection issues studied may involve the selection of appropriate compensatory measures during the period when an automatic fire detection or suppression system in a safety-related fire zone becomes inoperable. The compensatory measure can either be a 24-hour fire watch or an hourly fire patrol. The living fire PRA models were used to estimate the increase in risk associated with the fire protection issue in terms of changes in core damage frequency (CDF) and large early release frequency (LERF). In compliance with SDP at-power and the acceptance guidelines specified in RG 1.174, the fire protection issues in question can be grouped into four categories; red, yellow, white and green, in accordance with the guidelines developed for FD SDP. A 24-hour fire watch is suggested only required for the yellow condition, while an hourly fire patrol may be adopted for the white condition. More limiting requirement is suggested for the red condition, but no special consideration is needed for the green condition. For the calculation of risk measures, risk impacts from any additional fire scenarios that may have been introduced, as well as more severe initiating events and fire damages that may accompany the fire protection issue should be considered carefully. Examples are presented in this paper to illustrate the evaluation process. (authors)

Research Organization:
American Nuclear Society, 555 North Kensington Avenue, La Grange Park, IL 60526 (United States)
OSTI ID:
21160571
Resource Relation:
Conference: ICAPP'04: 2004 international congress on advances in nuclear power plants, Pittsburgh, PA (United States), 13-17 Jun 2004; Other Information: Country of input: France; 9 refs; Related Information: In: Proceedings of the 2004 international congress on advances in nuclear power plants - ICAPP'04, 2338 pages.
Country of Publication:
United States
Language:
English