skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: Detrimental effects of capacitance on high-resistance-grounded mine distribution systems

Journal Article · · IEEE Transactions on Industry Applications
; ; ;  [1]
  1. University of Kentucky, Lexington, KY (United States)

Modern underground coal mines can be very large, having a total connected load in excess of 15 000 hp. These, mines generally have many miles of high-power conveyor belts and 15 or more miles of high-voltage power cables at distribution voltages of 12.47, 13.2, 13.8, or 14.4 kV. The shielded cables used in mine power distribution systems have a significant level of capacitance, on the order of 110 pF/ft. This level of capacitance, in an extensive power distribution system at today's voltage levels, can cause significant charging currents during a ground fault. This paper addresses the potential detrimental effects of capacitance charging currents during line-to-ground faults in mine power distribution systems. A representative mine power system is modeled, and simulations with faults at various locations are conducted to evaluate the effects of this capacitance on the level of fault current and relay selectivity. This paper also includes results of capacitance measurements made on mine power feeder cables used to validate the simulation model.

OSTI ID:
20813265
Journal Information:
IEEE Transactions on Industry Applications, Vol. 42, Issue 5; ISSN 0093-9994
Country of Publication:
United States
Language:
English