Title: Airside HVAC BESTEST. Adaptation of ASHRAE RP 865 Airside HVAC Equipment Modeling Test Cases for ASHRAE Standard 140. Volume 1, Cases AE101-AE445

This report documents a set of diagnostic analytical verification cases for testing the ability of whole building simulation software to model the air distribution side of typical heating, ventilating and air conditioning (HVAC) equipment. These cases complement the unitary equipment cases included in American National Standards Institute (ANSI)/American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE) Standard 140, Standard Method of Test for the Evaluation of Building Energy Analysis Computer Programs, which test the ability to model the heat-transfer fluid side of HVAC equipment.
Authors:
 [1] ;  [2] ;  [3] ;  [4] ;  [4] ;  [5] ;  [5] ;  [6] ;  [7] ;  [8] ;  [8]
  1. J. Neymark & Associates, Golden, CO (United States)
  2. Mike D. Kennedy, Inc., Townsend, WA (United States)
  3. National Renewable Energy Lab. (NREL), Golden, CO (United States)
  4. AAON, Inc., Tulsa, OK (United States)
  5. GARD Analytics, Inc., Arlington Heights, IL (United States)
  6. Lawrence Berkeley National Lab. (LBNL), Berkeley, CA (United States)
  7. Thermal Energy System Specialists, Madison, WI (United States)
  8. Tsinghua Univ., Beijing (China)
Publication Date:
OSTI Identifier:
1244668
Report Number(s):
NREL/TP--5500-66000
DOE Contract Number:
AC36-08GO28308
Resource Type:
Technical Report
Research Org:
National Renewable Energy Lab. (NREL), Golden, CO (United States)
Sponsoring Org:
USDOE Office of Energy Efficiency and Renewable Energy (EERE), Building Technologies Office (EE-5B)
Country of Publication:
United States
Language:
English
Subject:
32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATION buildings; HVAC; ASHRAE; standard 140; commercial