Low-Flow Liquid Desiccant Air Conditioning: General Guidance and Site Considerations
Dehumidification or latent cooling in buildings is an area of growing interest that has been identified as needing more research and improved technologies for higher performance. Heating, ventilating, and air-conditioning (HVAC) systems typically expend excessive energy by using overcool-and-reheat strategies to dehumidify buildings. These systems first overcool ventilation air to remove moisture and then reheat the air to meet comfort requirements. Another common strategy incorporates solid desiccant rotors that remove moisture from the air more efficiently; however, these systems increase fan energy consumption because of the high airside pressure drop of solid desiccant rotors and can add heat of absorption to the ventilation air. Alternatively, liquid desiccant air-conditioning (LDAC) technology provides an innovative dehumidification solution that: (1) eliminates the need for overcooling and reheating from traditional cooling systems; and (2) avoids the increased fan energy and air heating from solid desiccant rotor systems.
- Research Organization:
- National Renewable Energy Lab. (NREL), Golden, CO (United States)
- Sponsoring Organization:
- USDOE Office of Energy Efficiency and Renewable Energy Building Technologies Office
- DOE Contract Number:
- AC36-08GO28308
- OSTI ID:
- 1159352
- Report Number(s):
- NREL/TP-5500-60655
- Country of Publication:
- United States
- Language:
- English
Similar Records
Review of liquid desiccant air dehumidification systems coupled with heat pump: System configurations, component design, and performance
Dehumidification and cooling loads from ventilation air