Title: Application of a Kalman filter to UF{sub 6} gaseous diffusion plant freezer/sublimer systems

Conference ·
OSTI ID:10119318

A signal is required to control the flow of UF{sub 6} in gaseous diffusion plant freezer/sublimer systems. The original strategy envisioned for deriving a flow signal was to take the derivative of the freezer/sublimer weigh cell signal. However, the derivative of the digitized weight signal is noisy, preventing good control. In addition, a bias is introduced into the weight derivative signal because a refrigerant is circulated through a shell-and-tube heat exchanger inside the freezer/sublimer. The weight of the refrigerant is included in the weight measured by the weigh cell. If the circulation rate of the refrigerent is not steady state, a bias exists. Measurements of upstream pressure, vessel pressure, and output to the system control valve are available to the control system. Thus, if the flow through the control valve is characterized properly by the measurements, a Kalman filter can be used in conjunction with these auxiliary inputs and the weigh cell input to overcome the noise and bias problem and provide an improve estimate of flow rate. A discussion of the development and the current status of a Kalman filter used for this application is given. 5 refs.

Research Organization:
Oak Ridge National Lab., TN (United States)
Sponsoring Organization:
USDOE, Washington, DC (United States)
DOE Contract Number:
AC05-84OR21400
OSTI ID:
10119318
Report Number(s):
CONF-920310-1; ON: DE92007238
Resource Relation:
Conference: American Institute of Chemical Engineers (AIChE) spring meeting,New Orleans, LA (United States),29 Mar - 2 Apr 1992; Other Information: PBD: Mar 1992
Country of Publication:
United States
Language:
English