Faults in air-cooled vapor compression air-conditioning systems are known to reduce performance, including efficiency, capacity, and lifespan. Their effects have been studied, and fault detection and diagnostic (FDD) methods have been developed as tools for field technicians to install or repair systems, or for monitoring to alert operators to the fault’s presence. Most of this work has focused on faults that occur singly. It is likely that in some systems, multiple faults occur simultaneously, but it is uncertain what effects this may have on diagnostics. Here, this paper describes a laboratory study of a split system air source heat pump in which combinations of two, three, and four simultaneous faults occur. The study includes all combinations of: improper evaporator airflow; overcharge or undercharge of refrigerant; liquid line restrictions; and non-condensable gas in the refrigerant, each at multiple fault intensities. Fault features – those characteristics that can be determined from measurements, for use in diagnostics – are analyzed, and the key fault features are presented. A robust existing method for determining refrigerant charge, the virtual refrigerant charge sensor (VRC) is tested using the multiple fault data, in order to understand how its performance is impacted by the combined faults. The VRC performs well, typically able to correctly determine whether a system is undercharged or overcharged, but the magnitude estimates are impacted. The results suggest that simple subcooling-based methods of charging a system are likely to provide unsatisfactory results when other faults are present.
- Research Organization:
- Univ. of Nebraska, Lincoln, NE (United States); University of Nebraska - Lincoln, Omaha, NE (United States)
- Sponsoring Organization:
- USDOE Office of Energy Efficiency and Renewable Energy (EERE); USDOE Office of Energy Efficiency and Renewable Energy (EERE), Energy Efficiency Office. Building Technologies Office
- Grant/Contract Number:
- EE0008689
- OSTI ID:
- 1977079
- Journal Information:
- Energy and Buildings, Journal Name: Energy and Buildings Journal Issue: C Vol. 251; ISSN 0378-7788
- Publisher:
- ElsevierCopyright Statement
- Country of Publication:
- United States
- Language:
- English
Similar Records
Experimental study of liquid line temperature drop as a fault feature for detecting severe liquid line restrictions in residential air conditioning systems
Multiple simultaneous faults’ impacts on air-conditioner behavior and performance of a charge diagnostic method
Related Subjects
Construction & Building Technology
Energy & Fuels
Engineering
Feature selection
Measurement variables
Residential air source heat pump
Residential air source heat pump
simultaneous faults
superheat
subcooling
measurement variables
feature selection
Simultaneous faults
Subcooling
Superheat