Root Cause Analysis of AC Overcurrent in July 2020 San Fernando Disturbance
- Univ. of South Florida, Tampa, FL (United States); University of South Florida
- Univ. of South Florida, Tampa, FL (United States)
On July 7 2020, approximately 1,000 MW reduction in solar photovoltaic (PV) output was experienced by the bulk power system in Southern California after a three-phase fault. Disturbance analysis indicates that instantaneous AC current caused inverter tripping. The projection of the root cause of AC overcurrent from the NERC report is that inverter current control is not tight. This letter provides a quantitative analysis on ac overcurrent and addresses the following questions: (i) what type of current controls may lead to ac overcurrent; and (ii) how controller parameters and grid strength influence ac overcurrent. Here, the letter provides frequency-domain analysis and time-domain simulation results of a grid-integrated inverter to illustrate the effect of control parameters and grid strength on ac overcurrent.
- Research Organization:
- Univ. of South Florida, Tampa, FL (United States)
- Sponsoring Organization:
- USDOE Office of Energy Efficiency and Renewable Energy (EERE), Renewable Power Office. Solar Energy Technologies Office
- Grant/Contract Number:
- EE0008771
- OSTI ID:
- 1810046
- Journal Information:
- IEEE Transactions on Power Systems, Journal Name: IEEE Transactions on Power Systems Journal Issue: 5 Vol. 36; ISSN 0885-8950
- Publisher:
- IEEECopyright Statement
- Country of Publication:
- United States
- Language:
- English
Overview of Control and Grid Synchronization for Distributed Power Generation Systems
|
journal | October 2006 |
Stationary frame current regulation of PWM inverters with zero steady-state error
|
journal | May 2003 |
Subcycle Overvoltage Dynamics in Solar PVs
|
journal | June 2021 |
Similar Records
Field testing of overcurrent trip units for low voltage circuit breakers used in DC applications
Flexible inverse overcurrent relaying using a microprocessor