You need JavaScript to view this

Dimensioning of flanged heat exchangers using the CYRANO software: pure refrigerants and mixtures; Dimensionnement des batteries a ailettes a l`aide du logiciel CYRANO: frigorigenes purs et melanges

Abstract

A software for the dimensioning and simulation of flanged heat exchangers is presented. This software divides the exchanger into pipe sections in which local values of physical properties of fluids and thermal exchange coefficients are used, and for which individual thermal-hydraulic performances are determined. CYRANO can be used for condensers, evaporators and monophase exchanges, with refrigerants like water, R22, R134a and R32/R125/R134a mixtures. The software can be used also in the case of specified complex circuits, equipped with smooth or grooved pipes and with smooth continuous, corrugated or slatted flanges with non-homogeneous air temperature and velocity distributions. The validation of CYRANO was performed on 7 exchangers with and without humidity condensation on the flanges. Comparisons with test results show that the average of errors in exchanged powers is of about 5%, and of about 30% in the case of internal pressure drops. Some simulations of exchangers with HFC mixtures are also presented. (J.S.) 34 refs.
Authors:
Bensafi, A; Borg, S [1] 
  1. CETIAT, Centre Technique des Industries Aerauliques et Thermiques, 69 - Villeurbanne (France)
Publication Date:
Dec 31, 1997
Product Type:
Conference
Report Number:
ETDE-FR-99713635; CONF-9701113-
Reference Number:
SCA: 420400; 990200; PA: FRC-98:004903; EDB-99:031212; SN: 98002035274
Resource Relation:
Conference: Workshop on recent evolutions of refrigerating machineries and heat pumps, Journee d`etudes ``Evolutions recentes des machines a froid et thermopompes``, France (France), 29 Jan 1997; Other Information: PBD: 1997; Related Information: Is Part Of Recent evolutions of refrigerating machineries and heat pumps; PB: 204 p.; Evolutions recentes des machines a froid et thermopompes
Subject:
42 ENGINEERING NOT INCLUDED IN OTHER CATEGORIES; 99 MATHEMATICS, COMPUTERS, INFORMATION SCIENCE, MANAGEMENT, LAW, MISCELLANEOUS; HEAT EXCHANGERS; COMPUTERIZED SIMULATION; C CODES; EVAPORATORS; VAPOR CONDENSERS; REFRIGERANTS; HEAT TRANSFER; ITERATIVE METHODS; FLUID FLOW; PRESSURE DROP; THERMODYNAMIC PROPERTIES; VAPOR CONDENSATION; VALIDATION
OSTI ID:
316703
Research Organizations:
Societe Francaise des Thermiciens, 75 - Paris (France)
Country of Origin:
France
Language:
French
Other Identifying Numbers:
Other: ON: DE99713635; TRN: FR9804903
Availability:
OSTI as DE99713635
Submitting Site:
FR
Size:
pp. 97-112
Announcement Date:
Mar 19, 1999

Citation Formats

Bensafi, A, and Borg, S. Dimensioning of flanged heat exchangers using the CYRANO software: pure refrigerants and mixtures; Dimensionnement des batteries a ailettes a l`aide du logiciel CYRANO: frigorigenes purs et melanges. France: N. p., 1997. Web.
Bensafi, A, & Borg, S. Dimensioning of flanged heat exchangers using the CYRANO software: pure refrigerants and mixtures; Dimensionnement des batteries a ailettes a l`aide du logiciel CYRANO: frigorigenes purs et melanges. France.
Bensafi, A, and Borg, S. 1997. "Dimensioning of flanged heat exchangers using the CYRANO software: pure refrigerants and mixtures; Dimensionnement des batteries a ailettes a l`aide du logiciel CYRANO: frigorigenes purs et melanges." France.
@misc{etde_316703,
title = {Dimensioning of flanged heat exchangers using the CYRANO software: pure refrigerants and mixtures; Dimensionnement des batteries a ailettes a l`aide du logiciel CYRANO: frigorigenes purs et melanges}
author = {Bensafi, A, and Borg, S}
abstractNote = {A software for the dimensioning and simulation of flanged heat exchangers is presented. This software divides the exchanger into pipe sections in which local values of physical properties of fluids and thermal exchange coefficients are used, and for which individual thermal-hydraulic performances are determined. CYRANO can be used for condensers, evaporators and monophase exchanges, with refrigerants like water, R22, R134a and R32/R125/R134a mixtures. The software can be used also in the case of specified complex circuits, equipped with smooth or grooved pipes and with smooth continuous, corrugated or slatted flanges with non-homogeneous air temperature and velocity distributions. The validation of CYRANO was performed on 7 exchangers with and without humidity condensation on the flanges. Comparisons with test results show that the average of errors in exchanged powers is of about 5%, and of about 30% in the case of internal pressure drops. Some simulations of exchangers with HFC mixtures are also presented. (J.S.) 34 refs.}
place = {France}
year = {1997}
month = {Dec}
}