Each unit of all the French nuclear power plant is equipped with two diesel emergency generator sets., For the totality of standards PWRs of 900 MWe, they are identical. We present in this communication the most significative failures met with diesel engines on operating units, such as rupture of fuel injection pipes, breaking of the connecting rods, and cylinder lubrication failures. All these incidents, which affected the emergency power sources of concerned units, had generic characteristics. In view of their potential consequences, it was proceeded in each case to an immediate control of the components concerned of all PWR 900 MWe diesel engines. At the same time, studies were started as to what modifications would permit to solve rapidly each one of the problems met with. (authors)
Authors:
Dredemis, Geoffroy; Jude, Francois [1] 
  1. Commissariat a l'Energie Atomique, centre d'Etudes Nucleaires de Fontenay-aux-Roses, Institut de Protection et Surete Nucleaire, Departement d'Analyse de Surete, B.P. No. 6, 92260 Fontenay-aux-Roses (France)
Publication Date:
Feb 15, 1986
Product Type:
Conference
Report Number:
NEA-CSNI-R-1986-115
Resource Relation:
Conference: CSNI specialist meeting on operating experience relating to on-site electric power sources, London (United Kingdom), 16-18 Oct 1985; Related Information: In: Operating experience relating to on-site electric power sources. Proceedings of a Specialist Meeting| 399 p.
Subject:
21 SPECIFIC NUCLEAR REACTORS AND ASSOCIATED PLANTS; 42 ENGINEERING; BLAYAIS-3 REACTOR; CRUAS-1 REACTOR; DAMAGE; DAMPIERRE-4 REACTOR; DIESEL ENGINES; ELECTRIC GENERATORS; FAILURE MODE ANALYSIS; FESSENHEIM-1 REACTOR; FUEL INJECTION SYSTEMS; IN-SERVICE INSPECTION; LUBRICATION; ON-SITE POWER GENERATION; RELIABILITY
OSTI ID:
22507819
Research Organizations:
Organisation for Economic Co-Operation and Development, Nuclear Energy Agency - OECD/NEA, Committee on the Safety of Nuclear Installations - CSNI, 46 quai Alphonse Le Gallo, 92100 Boulogne Billancourt (France)
Country of Origin:
NEA
Language:
English
Other Identifying Numbers:
TRN: XN1600266078394
Availability:
Available from INIS in electronic form
Submitting Site:
INIS
Size:
page(s) 67-73
Announcement Date:
Aug 24, 2016

Citation Formats

Dredemis, Geoffroy, and Jude, Francois. Main problems experienced on diesel generators of French 900 MWe operating units. NEA: N. p., 1986. Web.
Dredemis, Geoffroy, & Jude, Francois. Main problems experienced on diesel generators of French 900 MWe operating units. NEA.
Dredemis, Geoffroy, and Jude, Francois. 1986. "Main problems experienced on diesel generators of French 900 MWe operating units." NEA.
@misc{etde_22507819,
title = {Main problems experienced on diesel generators of French 900 MWe operating units}
author = {Dredemis, Geoffroy, and Jude, Francois}
abstractNote = {Each unit of all the French nuclear power plant is equipped with two diesel emergency generator sets., For the totality of standards PWRs of 900 MWe, they are identical. We present in this communication the most significative failures met with diesel engines on operating units, such as rupture of fuel injection pipes, breaking of the connecting rods, and cylinder lubrication failures. All these incidents, which affected the emergency power sources of concerned units, had generic characteristics. In view of their potential consequences, it was proceeded in each case to an immediate control of the components concerned of all PWR 900 MWe diesel engines. At the same time, studies were started as to what modifications would permit to solve rapidly each one of the problems met with. (authors)}
place = {NEA}
year = {1986}
month = {Feb}
}