Abstract
In the suburb of Herning, Snejbjerg, an experiment has been executed which implied a lowering of the flow temperature in the district heating network from 80 to 75 and 70 deg. C respectively. The effect regarding flow, temperature and pressure was registered and it could be proved that both the network and the user installations could be operated at such low temperatures. In continuation, an extensive analysis of the network was carried out. A considerable saving in the formn of a reduced heat loss from the network can be anticipated. Minor increase in the electricity consumption for pumping has to be anticipated, as the flow will increase due to the fact, that the return temperature is expected to be unchanged. (AB).
Citation Formats
None.
Demonstration project for low-temperature combined power and heat in Herning; Demonstrationsprojekt for lavtemperaturkraftvarme i Herning.
Denmark: N. p.,
1991.
Web.
None.
Demonstration project for low-temperature combined power and heat in Herning; Demonstrationsprojekt for lavtemperaturkraftvarme i Herning.
Denmark.
None.
1991.
"Demonstration project for low-temperature combined power and heat in Herning; Demonstrationsprojekt for lavtemperaturkraftvarme i Herning."
Denmark.
@misc{etde_10133709,
title = {Demonstration project for low-temperature combined power and heat in Herning; Demonstrationsprojekt for lavtemperaturkraftvarme i Herning}
author = {None}
abstractNote = {In the suburb of Herning, Snejbjerg, an experiment has been executed which implied a lowering of the flow temperature in the district heating network from 80 to 75 and 70 deg. C respectively. The effect regarding flow, temperature and pressure was registered and it could be proved that both the network and the user installations could be operated at such low temperatures. In continuation, an extensive analysis of the network was carried out. A considerable saving in the formn of a reduced heat loss from the network can be anticipated. Minor increase in the electricity consumption for pumping has to be anticipated, as the flow will increase due to the fact, that the return temperature is expected to be unchanged. (AB).}
place = {Denmark}
year = {1991}
month = {Apr}
}
title = {Demonstration project for low-temperature combined power and heat in Herning; Demonstrationsprojekt for lavtemperaturkraftvarme i Herning}
author = {None}
abstractNote = {In the suburb of Herning, Snejbjerg, an experiment has been executed which implied a lowering of the flow temperature in the district heating network from 80 to 75 and 70 deg. C respectively. The effect regarding flow, temperature and pressure was registered and it could be proved that both the network and the user installations could be operated at such low temperatures. In continuation, an extensive analysis of the network was carried out. A considerable saving in the formn of a reduced heat loss from the network can be anticipated. Minor increase in the electricity consumption for pumping has to be anticipated, as the flow will increase due to the fact, that the return temperature is expected to be unchanged. (AB).}
place = {Denmark}
year = {1991}
month = {Apr}
}