You need JavaScript to view this

Testing of a new method of thermographic examination of district heating pipes; Afproevning af ny metode ved termografering af fjernvarmeledninger

Abstract

Formulas were developed for determination of loss of heat in district heating pipes on the basis of thermographic examinations. The standard deviation for loss of heat defined on the basis of thermography is approx 55 W/m. The purpose of the present examination has been to test the method from project report no. 32 ``Thermographic examination of district heating pipes`` on an actual district heating network. The conclusion is that estimation of loss of heat on the basis of thermographic data definitely seems to be a qualified method for estimating and deciding the priority of the renovation work for a district heating network. Reduction of uncertainty can be obtained by carrying out more examinations on the same section, possibly at different times, to minimize uncertainties arising from climatic affects. The thermographic examination can be supplemented with thermometer measurement on the surfacing. The examination shows, however, that both methods would presumably lead to the same priority of renovation work. (AB).
Publication Date:
Nov 01, 1991
Product Type:
Miscellaneous
Report Number:
NEI-DK-767
Reference Number:
SCA: 320603; PA: DK-92:001144; SN: 92000700249
Resource Relation:
Other Information: DN: EFP-87; PBD: Nov 1991; Related Information: Energiministeriets Energiforskninsprogram. Fjernvarme og produktion af el og varme
Subject:
32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATION; DISTRICT HEATING; THERMOGRAPHY; PIPES; HEAT LOSSES; MAINTENANCE; 320603; PUBLIC UTILITIES
OSTI ID:
10133522
Research Organizations:
Bjeld and Lauridsen A/S, Frederica (Denmark); Hoejlund Rasmussen (B.) Raadgivende Ingenioerer A/S, Copenhagen (Denmark)
Country of Origin:
Denmark
Language:
Danish
Other Identifying Numbers:
Other: ON: DE92793305; CNN: Contract EM-1413/87-2; TRN: DK9201144
Availability:
OSTI; NTIS (US Sales Only)
Submitting Site:
DK
Size:
57 p.
Announcement Date:
Jul 04, 2005

Citation Formats

Melballe, J A, and Hansen, K E. Testing of a new method of thermographic examination of district heating pipes; Afproevning af ny metode ved termografering af fjernvarmeledninger. Denmark: N. p., 1991. Web.
Melballe, J A, & Hansen, K E. Testing of a new method of thermographic examination of district heating pipes; Afproevning af ny metode ved termografering af fjernvarmeledninger. Denmark.
Melballe, J A, and Hansen, K E. 1991. "Testing of a new method of thermographic examination of district heating pipes; Afproevning af ny metode ved termografering af fjernvarmeledninger." Denmark.
@misc{etde_10133522,
title = {Testing of a new method of thermographic examination of district heating pipes; Afproevning af ny metode ved termografering af fjernvarmeledninger}
author = {Melballe, J A, and Hansen, K E}
abstractNote = {Formulas were developed for determination of loss of heat in district heating pipes on the basis of thermographic examinations. The standard deviation for loss of heat defined on the basis of thermography is approx 55 W/m. The purpose of the present examination has been to test the method from project report no. 32 ``Thermographic examination of district heating pipes`` on an actual district heating network. The conclusion is that estimation of loss of heat on the basis of thermographic data definitely seems to be a qualified method for estimating and deciding the priority of the renovation work for a district heating network. Reduction of uncertainty can be obtained by carrying out more examinations on the same section, possibly at different times, to minimize uncertainties arising from climatic affects. The thermographic examination can be supplemented with thermometer measurement on the surfacing. The examination shows, however, that both methods would presumably lead to the same priority of renovation work. (AB).}
place = {Denmark}
year = {1991}
month = {Nov}
}