Title: High Technology Centrifugal Compressor for Commercial Air Conditioning Systems

Abstract

R&D Dynamics, Bloomfield, CT in partnership with the State of Connecticut has been developing a high technology, oil-free, energy-efficient centrifugal compressor called CENVA for commercial air conditioning systems under a program funded by the US Department of Energy. The CENVA compressor applies the foil bearing technology used in all modern aircraft, civil and military, air conditioning systems. The CENVA compressor will enhance the efficiency of water and air cooled chillers, packaged roof top units, and other air conditioning systems by providing an 18% reduction in energy consumption in the unit capacity range of 25 to 350 tons of refrigeration The technical approach for CENVA involved the design and development of a high-speed, oil-free foil gas bearing-supported two-stage centrifugal compressor, CENVA encompassed the following high technologies, which are not currently utilized in commercial air conditioning systems: Foil gas bearings operating in HFC-134a; Efficient centrifugal impellers and diffusers; High speed motors and drives; and System integration of above technologies. Extensive design, development and testing efforts were carried out. Significant accomplishments achieved under this program are: (1) A total of 26 builds and over 200 tests were successfully completed with successively improved designs; (2) Use of foil gas bearings in refrigerant R134a wasmore » successfully proven; (3) A high speed, high power permanent magnet motor was developed; (4) An encoder was used for signal feedback between motor and controller. Due to temperature limitations of the encoder, the compressor could not operate at higher speed and in turn at higher pressure. In order to alleviate this problem a unique sensorless controller was developed; (5) This controller has successfully been tested as stand alone; however, it has not yet been integrated and tested as a system; (6) The compressor successfully operated at water cooled condensing temperatures Due to temperature limitations of the encoder, it could not be operated at air cooled condensing temperatures. (7) The two-stage impellers/diffusers worked well separately but combined did not match well.« less

Authors:
Publication Date:
Research Org.:
Connecticut State Of Office of Policy And Management
Sponsoring Org.:
USDOE
OSTI Identifier:
902086
DOE Contract Number:
FC26-02GO12014
Resource Type:
Technical Report
Country of Publication:
United States
Language:
English
Subject:
32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATION; AIR CONDITIONING; AIRCRAFT; BEARINGS; COMPRESSORS; DIFFUSERS; EFFICIENCY; ENERGY CONSUMPTION; FEEDBACK; GAS BEARINGS; MOTORS; PERMANENT MAGNETS; REFRIGERANTS; REFRIGERATION; ROOFS; TESTING; VELOCITY; WATER

Citation Formats

Ruckes, John. High Technology Centrifugal Compressor for Commercial Air Conditioning Systems. United States: N. p., 2006. Web. doi:10.2172/902086.
Ruckes, John. High Technology Centrifugal Compressor for Commercial Air Conditioning Systems. United States. doi:10.2172/902086.
Ruckes, John. Sat . "High Technology Centrifugal Compressor for Commercial Air Conditioning Systems". United States. doi:10.2172/902086. https://www.osti.gov/servlets/purl/902086.
@article{osti_902086,
title = {High Technology Centrifugal Compressor for Commercial Air Conditioning Systems},
author = {Ruckes, John},
abstractNote = {R&D Dynamics, Bloomfield, CT in partnership with the State of Connecticut has been developing a high technology, oil-free, energy-efficient centrifugal compressor called CENVA for commercial air conditioning systems under a program funded by the US Department of Energy. The CENVA compressor applies the foil bearing technology used in all modern aircraft, civil and military, air conditioning systems. The CENVA compressor will enhance the efficiency of water and air cooled chillers, packaged roof top units, and other air conditioning systems by providing an 18% reduction in energy consumption in the unit capacity range of 25 to 350 tons of refrigeration The technical approach for CENVA involved the design and development of a high-speed, oil-free foil gas bearing-supported two-stage centrifugal compressor, CENVA encompassed the following high technologies, which are not currently utilized in commercial air conditioning systems: Foil gas bearings operating in HFC-134a; Efficient centrifugal impellers and diffusers; High speed motors and drives; and System integration of above technologies. Extensive design, development and testing efforts were carried out. Significant accomplishments achieved under this program are: (1) A total of 26 builds and over 200 tests were successfully completed with successively improved designs; (2) Use of foil gas bearings in refrigerant R134a was successfully proven; (3) A high speed, high power permanent magnet motor was developed; (4) An encoder was used for signal feedback between motor and controller. Due to temperature limitations of the encoder, the compressor could not operate at higher speed and in turn at higher pressure. In order to alleviate this problem a unique sensorless controller was developed; (5) This controller has successfully been tested as stand alone; however, it has not yet been integrated and tested as a system; (6) The compressor successfully operated at water cooled condensing temperatures Due to temperature limitations of the encoder, it could not be operated at air cooled condensing temperatures. (7) The two-stage impellers/diffusers worked well separately but combined did not match well.},
doi = {10.2172/902086},
journal = {},
number = ,
volume = ,
place = {United States},
year = {Sat Apr 15 00:00:00 EDT 2006},
month = {Sat Apr 15 00:00:00 EDT 2006}
}

Technical Report:

Save / Share:
  • This report summarizes the results of the test and evaluation of a prototype rotary-screw compressor design. The UMTA-funded RandD program consisted of two phases. The objectives of the first phase were to ascertain the extent of the problems with current bus air-conditioning systems and to determine the feasibility of adapting alternative compressor technology for use in transit buses. This work was carried out by the (Garrett) AiResearch Manufacturing Co. of Torrance, California and Dunham-Bush, Inc. of W. Hartford, Connecticut and has been documented in UMTA Report No. CA-06-0145-80-1 (NTIS No. PB-215-502). The second phase was to test a prototype alternativemore » compressor under a wide range of simulated, and actual, bus revenue service environmental conditions and was also conducted by Dunham-Bush, Inc. It is the results of this effort that are documented in this report.« less
  • This document presents the methods and procedures used and the results obtained in the design, fabrication, and testing of a rotary vane type compressor operated on air cycle thermodynamics. The history and results of the testing of a similar expander are summarized and the full report of that work is referenced. The machine design used was based on one patented by Ecton Corporation. The goal of the reported effort was to demonstrate the attainable efficiencies of these machines. Appropriate test rigs were assembled and the machines were tested at various operating conditions. The compressor testing did not achieve the fullmore » design speed because of time constraints but important data was obtained at 87% speed (3000 rpm). The maximum measured total efficiencies were 78% for the expander and 71% for the compressor. Various design improvements which may yield improved performance were identified and reported.« less
  • This report describes the development and testing of a low/zero stratospheric ozone-depletion mobile air conditioning system. The projected goals of the project have been attained and exceeded. A vehicle has been dynamically load tested with the OEM system, and retrofitted and tested with the ROVAC air conditioning system. Further refinement of the prototype A/C system, particularly in the new refrigerants available, should provide improved performance. A brassboard test system has also been completed. Tests using a modified residential compressor have shown that when R-142b is used as the refrigerant, the new system essentially matched the performance of the R-12 systemmore » during the pull-down and 55 mph portions of the test. 5 refs., 7 figs.« less
  • The objectives of this project were: (a) to develop, test, and analyze a retrofit improvement in commercial air conditioning systems, and (b) to use commercially available equipment and existing labor skills in order to enhance near term adoption. The target application for this improvement is the commercial sector. However, simplifications to the improvement make it applicable to the residential sector also. To accomplish these objectives, four distinct efforts were required: design a prototype system to be used for testing; formulate a test plan and design an appropriate instrumentation system; install the prototype system and its instrumentation, monitor system performance; andmore » evaluate the performance and economics of the system. The execution and results of each of these effects are described.« less