Leakage diagnostics, sealant longevity, sizing and technologytransfer in residential thermal distribution systems: Part II.Residential thermal Distribution Systesm, Phase VI FinalReport
Abstract
This report builds on and extends our previous efforts as described in "Leakage Diagnostics, Sealant Longevity, Sizing and Technology Transfer in Residential Thermal Distribution Systems- CIEE Residential Thermal Distribution Systems Phase V Final Report, October 1997". New developments include defining combined duct and equipment efficiencies in a concept called "Tons At the Register" and on performance issues related to field use of the aerosol sealant technology. Some of the key results discussed in this report include: o Register, boot and air handler cabinet leakage can often represent a significant fraction of the total duct leakage in new construction. Because of the large range of pressures in duct systems an accurate characterization may require separating these components through improved leakage testing. o Conventional duct tape failed our accelerated longevity testing and is not, therefore, considered generally acceptable for use in sealing duct systems. Many other tapes and sealing approaches are available and practical and have passed our longevity tests. o Simulations of summer temperature pull-down time have shown that duct system improvements can be combined with equipment downsizing to save first cost, energy consumption, and peak power and still provide equivalent or superior comfort. o Air conditioner name plate capacity ratingsmore »
- Authors:
- Publication Date:
- Research Org.:
- Lawrence Berkeley National Lab. (LBNL), Berkeley, CA (United States)
- Sponsoring Org.:
- USDOE Office of Energy Efficiency and Renewable Energy (EERE)
- OSTI Identifier:
- 8681
- Report Number(s):
- LBNL-42691-Part-II
ON: DE00008681
- DOE Contract Number:
- AC03-76SF00098
- Resource Type:
- Technical Report
- Country of Publication:
- United States
- Language:
- English
- Subject:
- 32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATION; Leak Testing; Sealing Materials; Service Life; Size; Technology Transfer; Residential Buildings; Heat Distribution Systems; Ducts
Citation Formats
Buchanan, C., Modera, M., Sherman, M., Siegel, J., Walker, I., and Wang, D.. Leakage diagnostics, sealant longevity, sizing and technologytransfer in residential thermal distribution systems: Part II.Residential thermal Distribution Systesm, Phase VI FinalReport. United States: N. p., 1998.
Web. doi:10.2172/8681.
Buchanan, C., Modera, M., Sherman, M., Siegel, J., Walker, I., & Wang, D.. Leakage diagnostics, sealant longevity, sizing and technologytransfer in residential thermal distribution systems: Part II.Residential thermal Distribution Systesm, Phase VI FinalReport. United States. doi:10.2172/8681.
Buchanan, C., Modera, M., Sherman, M., Siegel, J., Walker, I., and Wang, D.. Tue .
"Leakage diagnostics, sealant longevity, sizing and technologytransfer in residential thermal distribution systems: Part II.Residential thermal Distribution Systesm, Phase VI FinalReport". United States.
doi:10.2172/8681. https://www.osti.gov/servlets/purl/8681.
@article{osti_8681,
title = {Leakage diagnostics, sealant longevity, sizing and technologytransfer in residential thermal distribution systems: Part II.Residential thermal Distribution Systesm, Phase VI FinalReport},
author = {Buchanan, C. and Modera, M. and Sherman, M. and Siegel, J. and Walker, I. and Wang, D.},
abstractNote = {This report builds on and extends our previous efforts as described in "Leakage Diagnostics, Sealant Longevity, Sizing and Technology Transfer in Residential Thermal Distribution Systems- CIEE Residential Thermal Distribution Systems Phase V Final Report, October 1997". New developments include defining combined duct and equipment efficiencies in a concept called "Tons At the Register" and on performance issues related to field use of the aerosol sealant technology. Some of the key results discussed in this report include: o Register, boot and air handler cabinet leakage can often represent a significant fraction of the total duct leakage in new construction. Because of the large range of pressures in duct systems an accurate characterization may require separating these components through improved leakage testing. o Conventional duct tape failed our accelerated longevity testing and is not, therefore, considered generally acceptable for use in sealing duct systems. Many other tapes and sealing approaches are available and practical and have passed our longevity tests. o Simulations of summer temperature pull-down time have shown that duct system improvements can be combined with equipment downsizing to save first cost, energy consumption, and peak power and still provide equivalent or superior comfort. o Air conditioner name plate capacity ratings alone are a poor indicator of how much cooling will actually be delivered to the conditioned space. Duct system efficiency can have as large an impact on performance as variations in SEER. o Mechanical duct cleaning techniques do not have an adverse impact on the ducts sealed with the Aerosol sealant. The material typically used in Aerosol sealing techniques does not appear to present a health or safety hazard. Results from this study were used by the California Energy Commission in the formation of the current Energy Efficiency Standards for Low-Rise Residential Buildings (CEC, (1998)), often referred to as Title 24. Current information on ducts and thermal distribution research can be found at http://ducts.lbl.gov},
doi = {10.2172/8681},
journal = {},
number = ,
volume = ,
place = {United States},
year = {Tue Dec 01 00:00:00 EST 1998},
month = {Tue Dec 01 00:00:00 EST 1998}
}
-
This field study concentrated on measurement of duct leakage to outside the conditioned space because this is most useful in energy calculations. For room by room load/comfort requirements, the total duct leakage (including leaks to conditioned space) is more appropriate, particularly for additional comfort considerations. The objective of this field study is to help to identify major sources of uncertainty and to quantify the trade offs between different test methods. The identification of the areas requiring significant improvement will aid in future development of duct leakage test methods. For example, during the course of this study a new method formore »
-
Distribution effectiveness and impacts on equipment sizing for residential thermal distribution systems
This report was prepared as a result of work sponsored by the California Energy Commission (Commission), through a contract with the Regents of the University of California, California Institute for Energy Efficiency (CIEE). It does not necessarily represent the views of the Commission, its employees, the State of California, The Regents, or CIEE. The Commission, the Regents, the State of California, CIEE, their employees, contractors, and subcontractors, make no warranty, express or implied, and assume no legal liability for the information in this report; nor does any party represent that the use of this information will not infringe upon privatelymore » -
Thermal Distribution Program Plan: Part 1, Forced-air distribution systems in residential and small commercial buildings and Part 2, Hydronic and radiant heating and cooling systems
This document is intended to serve as a basis for the US Department of Energy's (DOE's) multilayer plan for research on thermal distribution and utilization (TDU). In this document, the areas of research included under the heading of thermal distribution and utilization are defined, their benefits are shown, and a ten-year program of research is recommended. Part I of the Plan concentrates on forced-air thermal distribution systems in residences and small commercial buildings. Part II covers hydronic and radiant systems. TDU research refers to the study of the phenomena associated with the transport of heat and cooling effect from themore » -
Longevity of duct tape in residential air distribution systems: 1-D, 2-D, and 3-D joints
The aging tests conducted so far showed that duct tape tends to degrade in its performance as the joint it is applied to requires a geometrical description of a higher number of space dimensions (1-D, 2-D, 3-D). One-dimensional joints are the easiest to seal with duct tape, and thus the least to experience failure. Two-dimensional joints, such as the flexible duct core-to-collar joints tested in this study, are less likely to fail than three-dimensional collar-to-plenum joints, as the shrinkage could have a positive effect in tightening the joint. Three-dimensional joints are the toughest to seal and the most likely tomore » -
A collector sizing procedure for residential solar hot water systems with prescribed thermal performance requirements. Final report
A graphical procedure was developed based on the f-chart design method to determine whether solar domestic water heating systems proposed for use in the HUD Hot Water Initiative Program have sufficient collector area to provide 50% of the load as prescribed by the thermal performance requirements of the Program. The procedure was specifically developed for the 11 states participating in the HUD initiative (the New-England and Mid-Atlantic States and Florida), however, it should be applicable for the sizing of the collectors for solar water heaters in other locations with similar climates.