Title: An efficient cooling loop for connecting cryocooler to a helium reservoir

Abstract

The magnet system of the VENUS ECR Ion Source at LBNL has two 1.5-watt cryocoolers suspended in the cryostat vacuum. Helium vapor from the liquid reservoir is admitted to a finned condenser bolted to the cryocooler 2nd stage and returns as liquid via gravity. Small-diameter flexible tubes allow the cryocoolers to be located remotely from the reservoir. With 3.1 watts load, the helium reservoir is maintained at 4.35 K, 0.05K above the cryocooler temperature. Design, analysis, and performance are presented.

Authors:
; ; ; ;
Publication Date:
Research Org.:
Lawrence Berkeley National Lab. (LBNL), Berkeley, CA (United States)
Sponsoring Org.:
USDOE Director. Office of Science. Nuclear Physics (US)
OSTI Identifier:
819968
Report Number(s):
LBNL-53679
R&D Project: N88OPS; TRN: US0305635
DOE Contract Number:  
AC03-76SF00098
Resource Type:
Conference
Resource Relation:
Conference: 2003 Cryogenic Engineering Conference & International Cryogenic Materials Conference, Anchorage, AK (US), 09/22/2003--09/26/2003; Other Information: PBD: 21 Sep 2003
Country of Publication:
United States
Language:
English
Subject:
73 NUCLEAR PHYSICS AND RADIATION PHYSICS; CRYOGENICS; CRYOSTATS; DESIGN; ECR ION SOURCES; HELIUM; MAGNETS; PERFORMANCE

Citation Formats

Taylor, C.E., Abbott, C.S.R., Leitner, D., Leitner, M., and Lyneis, C.M. An efficient cooling loop for connecting cryocooler to a helium reservoir. United States: N. p., 2003. Web.
Taylor, C.E., Abbott, C.S.R., Leitner, D., Leitner, M., & Lyneis, C.M. An efficient cooling loop for connecting cryocooler to a helium reservoir. United States.
Taylor, C.E., Abbott, C.S.R., Leitner, D., Leitner, M., and Lyneis, C.M. Sun . "An efficient cooling loop for connecting cryocooler to a helium reservoir". United States. https://www.osti.gov/servlets/purl/819968.
@article{osti_819968,
title = {An efficient cooling loop for connecting cryocooler to a helium reservoir},
author = {Taylor, C.E. and Abbott, C.S.R. and Leitner, D. and Leitner, M. and Lyneis, C.M.},
abstractNote = {The magnet system of the VENUS ECR Ion Source at LBNL has two 1.5-watt cryocoolers suspended in the cryostat vacuum. Helium vapor from the liquid reservoir is admitted to a finned condenser bolted to the cryocooler 2nd stage and returns as liquid via gravity. Small-diameter flexible tubes allow the cryocoolers to be located remotely from the reservoir. With 3.1 watts load, the helium reservoir is maintained at 4.35 K, 0.05K above the cryocooler temperature. Design, analysis, and performance are presented.},
doi = {},
journal = {},
number = ,
volume = ,
place = {United States},
year = {2003},
month = {9}
}