ENGINEERING EVALUATION OF DOUBLE SHELL TANK (DST) VAPOR SPACE CONDENSATION & ANNULUS RELATIVE HUMIDITY
Abstract
An engineering evaluation of psychrometric conditions within the primary tank vapor space and the wall annulus of the twenty-eight double-shell tanks was conducted by the Hanford double-shell tank integrity project. The purpose of the evaluation was to identify conditions which can promote condensation on the primary liner surface and identify tanks whose wall annulus region exceeds recommended relative humidity limits. An engineering evaluation of Psychrometric conditions within the primary tank vapor space and the wall annulus of the twenty-eight DST's was conducted by the Hanford DSTIP. The purpose of the evaluation was to identify conditions which can promote condensation on the primary liner surface and identify tanks where the wall annulus region relative humidity exceeds recommended limits. The evaluations employed computer models of the twenty-eight DST's which modeled the heat and mass transfer mechanisms in the primary tank vapor space and annulus region. An evaluation of potential mitigation through ventilation system operations was also evaluated. The mitigation evaluation was intended to provide only preliminary evaluation of mitigation options. The Vapor Space Corrosion panel cautioned against implementation of quick fixes until the surface chemistry and corrosion mechanisms are better understood.
- Authors:
- Publication Date:
- Research Org.:
- CH2M (US)
- Sponsoring Org.:
- ENVIRONMENTAL MANAGEMENT (US)
- OSTI Identifier:
- 812322
- Report Number(s):
- RPP-12422, Rev.0
EDT-628470; TRN: US0303348
- DOE Contract Number:
- AC27-99RL14047
- Resource Type:
- Technical Report
- Resource Relation:
- Other Information: PBD: 23 Jun 2003
- Country of Publication:
- United States
- Language:
- English
- Subject:
- 12 MANAGEMENT OF RADIOACTIVE WASTES, AND NON-RADIOACTIVE WASTES FROM NUCLEAR FACILITIES; CORROSION; HUMIDITY; LINERS; MASS TRANSFER; MITIGATION; VENTILATION SYSTEMS; STORAGE FACILITIES; ANNULAR SPACE; VAPOR CONDENSATION; RADIOACTIVE WASTE STORAGE
Citation Formats
ANANTATMULA, R., DUNCAN, G., and OGDEN. ENGINEERING EVALUATION OF DOUBLE SHELL TANK (DST) VAPOR SPACE CONDENSATION & ANNULUS RELATIVE HUMIDITY. United States: N. p., 2003.
Web. doi:10.2172/812322.
ANANTATMULA, R., DUNCAN, G., & OGDEN. ENGINEERING EVALUATION OF DOUBLE SHELL TANK (DST) VAPOR SPACE CONDENSATION & ANNULUS RELATIVE HUMIDITY. United States. doi:10.2172/812322.
ANANTATMULA, R., DUNCAN, G., and OGDEN. Mon .
"ENGINEERING EVALUATION OF DOUBLE SHELL TANK (DST) VAPOR SPACE CONDENSATION & ANNULUS RELATIVE HUMIDITY". United States.
doi:10.2172/812322. https://www.osti.gov/servlets/purl/812322.
@article{osti_812322,
title = {ENGINEERING EVALUATION OF DOUBLE SHELL TANK (DST) VAPOR SPACE CONDENSATION & ANNULUS RELATIVE HUMIDITY},
author = {ANANTATMULA, R. and DUNCAN, G. and OGDEN},
abstractNote = {An engineering evaluation of psychrometric conditions within the primary tank vapor space and the wall annulus of the twenty-eight double-shell tanks was conducted by the Hanford double-shell tank integrity project. The purpose of the evaluation was to identify conditions which can promote condensation on the primary liner surface and identify tanks whose wall annulus region exceeds recommended relative humidity limits. An engineering evaluation of Psychrometric conditions within the primary tank vapor space and the wall annulus of the twenty-eight DST's was conducted by the Hanford DSTIP. The purpose of the evaluation was to identify conditions which can promote condensation on the primary liner surface and identify tanks where the wall annulus region relative humidity exceeds recommended limits. The evaluations employed computer models of the twenty-eight DST's which modeled the heat and mass transfer mechanisms in the primary tank vapor space and annulus region. An evaluation of potential mitigation through ventilation system operations was also evaluated. The mitigation evaluation was intended to provide only preliminary evaluation of mitigation options. The Vapor Space Corrosion panel cautioned against implementation of quick fixes until the surface chemistry and corrosion mechanisms are better understood.},
doi = {10.2172/812322},
journal = {},
number = ,
volume = ,
place = {United States},
year = {Mon Jun 23 00:00:00 EDT 2003},
month = {Mon Jun 23 00:00:00 EDT 2003}
}
-
This document presents the results of the hazard identification, evaluation, and control allocation for the use of the Oceaneering tank wall cleaning system to remove scale from the outside of the primary tank wall of 241-AY-101.
-
Safety evaluation for the oceaneering double shell tank (DST) annulus wall cleaning system
This document presents the results of the hazard identification, evaluation, and control allocation for the use of the Oceaneering tank wall cleaning system to remove scale from the outside of the primary tank wall of 241-AY-101. -
Single Shell Tank (SST) Retrieval Sequence & Double Shell Tank (DST) Space Evaluation
This document describes the baseline single-shell tank (SST) waste retrieval sequence for the River Protection Project updated for Fiscal Year 2002. The double-shell tank (DST) space evaluation presents projected DST needs for Hanford for additional DSTs. -
Single Shell Tank (SST) Retrieval Sequence & Double Shell Tank (DST) Space Evaluation
This document describes the baseline single-shell tank (SST) waste retrieval sequence for the River Protection Project updated for Fiscal Year 2002. The double-shell tank (DST) space evaluation presents projected DST needs for Hanford for additional DSTs. -