Title: Fire Protection Research Program at Sandia National Laboratories

Abstract

Sandia National Laboratories is executing a program for the Nuclear Regulatory Commission to provide data needed for confirmation of the suitability of current design standards and regulatory guides for fire protection and control in water reactor power plants. This paper summarizes the activities of this ongoing program through October 1980. Characterization of electrically initiated fires revealed a margin of safety in the separation criteria of Regulatory Guide 1.75 for such fires in IEEE-383 qualified cable. However, tests confirmed that these guidelines and standards are not sufficient, in themselves, to protect against exposure fires. This paper describes both small and full scale tests to assess the adequacy of fire retardant coatings and full scale tests on fire shields to determine their effectiveness. It also describes full scale tests to determine the effects of walls and ceilings on fire propagation between cable trays. Some small-scale scoping tests have been conducted to investigate the effects of varying the furnace pressure on cable penetration performance in the ASTM-E-119 Fire Test. The Sandia Fire Research Facility has been completed and a series of tests have been run to assess the effectiveness of Halon-1301 as a suppression system in extinguishing deep-seated cable-tray fires. It was foundmore » that given sufficient soak times Halon systems are effective in extinguishing such fires.« less

Authors:
Publication Date:
Research Org.:
Sandia National Labs., Albuquerque, NM (USA)
Sponsoring Org.:
USDOE
OSTI Identifier:
6986230
Report Number(s):
SAND-80-2422C; CONF-801053-4
TRN: 80-018661
DOE Contract Number:  
AC04-76DP00789
Resource Type:
Conference
Resource Relation:
Conference: 8. water reactor safety research information meeting, Gaithersburg, MD, USA, 27 Oct 1980
Country of Publication:
United States
Language:
English
Subject:
22 GENERAL STUDIES OF NUCLEAR REACTORS; NUCLEAR POWER PLANTS; FIRE PREVENTION; WATER COOLED REACTORS; ELECTRIC CABLES; FIRE EXTINGUISHERS; FIRE FIGHTING; SAFETY; CABLES; CONDUCTOR DEVICES; ELECTRICAL EQUIPMENT; EQUIPMENT; NUCLEAR FACILITIES; POWER PLANTS; REACTORS; THERMAL POWER PLANTS; 220900* - Nuclear Reactor Technology- Reactor Safety

Citation Formats

Klamerus, L. J. Fire Protection Research Program at Sandia National Laboratories. United States: N. p., 1980. Web.
Klamerus, L. J. Fire Protection Research Program at Sandia National Laboratories. United States.
Klamerus, L. J. 1980. "Fire Protection Research Program at Sandia National Laboratories". United States. https://www.osti.gov/servlets/purl/6986230.
@article{osti_6986230,
title = {Fire Protection Research Program at Sandia National Laboratories},
author = {Klamerus, L. J.},
abstractNote = {Sandia National Laboratories is executing a program for the Nuclear Regulatory Commission to provide data needed for confirmation of the suitability of current design standards and regulatory guides for fire protection and control in water reactor power plants. This paper summarizes the activities of this ongoing program through October 1980. Characterization of electrically initiated fires revealed a margin of safety in the separation criteria of Regulatory Guide 1.75 for such fires in IEEE-383 qualified cable. However, tests confirmed that these guidelines and standards are not sufficient, in themselves, to protect against exposure fires. This paper describes both small and full scale tests to assess the adequacy of fire retardant coatings and full scale tests on fire shields to determine their effectiveness. It also describes full scale tests to determine the effects of walls and ceilings on fire propagation between cable trays. Some small-scale scoping tests have been conducted to investigate the effects of varying the furnace pressure on cable penetration performance in the ASTM-E-119 Fire Test. The Sandia Fire Research Facility has been completed and a series of tests have been run to assess the effectiveness of Halon-1301 as a suppression system in extinguishing deep-seated cable-tray fires. It was found that given sufficient soak times Halon systems are effective in extinguishing such fires.},
doi = {},
url = {https://www.osti.gov/biblio/6986230}, journal = {},
number = ,
volume = ,
place = {United States},
year = {Tue Jan 01 00:00:00 EST 1980},
month = {Tue Jan 01 00:00:00 EST 1980}
}

Conference:
Other availability
Please see Document Availability for additional information on obtaining the full-text document. Library patrons may search WorldCat to identify libraries that hold this conference proceeding.

Save / Share: