Title: Cold energy release characteristics of an ice/air direct contact heat exchanger

Abstract

This paper deals with the cold energy release characteristics of an ice/air direct contact heat exchanger in a refined cold energy conveyance system. Characteristics of the outlet temperature, the humidity, and time history of released heat are examined when the initial height of the ice-cube-packed bed in the heat exchanger is changed. The following are the results obtained in these experiments: (1) Inlet air of 30 C is lowered to about 0 C by passing the air through the heat exchanger, and absolute humidity of the outlet air is reduced to about a quarter of that of the inlet air. (2) There is an optimum height of the ice-cube-packed bed for maximizing the amount of cold energy released. (3) This heat exchange method can supply about twice the amount of cold energy released by an ordinary fin-tube-type heat exchanger even if the air velocity in the heat exchanger is reduced to about 0.38 times that of the fin-tube-type heat exchanger.

Authors:
;  [1]; ; ;  [2]
  1. Hitachi Ltd., Ibaraki (Japan)
  2. Tokyo Electric Power Co., Yokohama (Japan)
Publication Date:
OSTI Identifier:
687603
Report Number(s):
CONF-980650-
Journal ID: ISSN 0001-2505; TRN: IM9944%%268
Resource Type:
Conference
Resource Relation:
Conference: 1998 ASHRAE summer annual meeting, Toronto (Canada), 20 Jun 1998; Other Information: PBD: 1998; Related Information: Is Part Of ASHRAE transactions 1998: Technical and symposium papers. Volume 104, Part 2; PB: 1511 p.
Country of Publication:
United States
Language:
English
Subject:
32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATION; 25 ENERGY STORAGE; AIR CONDITIONING; LATENT HEAT STORAGE; ICE; ENERGY CONSUMPTION; BUILDINGS; DIRECT CONTACT HEAT EXCHANGERS; PACKED BEDS; PNEUMATIC TRANSPORT; HEAT TRANSFER

Citation Formats

Ohira, Akiyoshi, Yanadori, Michio, Iwabuchi, Kunihiko, Kimura, Toshikatsu, and Tsubota, Yuji. Cold energy release characteristics of an ice/air direct contact heat exchanger. United States: N. p., 1998. Web.
Ohira, Akiyoshi, Yanadori, Michio, Iwabuchi, Kunihiko, Kimura, Toshikatsu, & Tsubota, Yuji. Cold energy release characteristics of an ice/air direct contact heat exchanger. United States.
Ohira, Akiyoshi, Yanadori, Michio, Iwabuchi, Kunihiko, Kimura, Toshikatsu, and Tsubota, Yuji. Thu . "Cold energy release characteristics of an ice/air direct contact heat exchanger". United States. doi:.
@article{osti_687603,
title = {Cold energy release characteristics of an ice/air direct contact heat exchanger},
author = {Ohira, Akiyoshi and Yanadori, Michio and Iwabuchi, Kunihiko and Kimura, Toshikatsu and Tsubota, Yuji},
abstractNote = {This paper deals with the cold energy release characteristics of an ice/air direct contact heat exchanger in a refined cold energy conveyance system. Characteristics of the outlet temperature, the humidity, and time history of released heat are examined when the initial height of the ice-cube-packed bed in the heat exchanger is changed. The following are the results obtained in these experiments: (1) Inlet air of 30 C is lowered to about 0 C by passing the air through the heat exchanger, and absolute humidity of the outlet air is reduced to about a quarter of that of the inlet air. (2) There is an optimum height of the ice-cube-packed bed for maximizing the amount of cold energy released. (3) This heat exchange method can supply about twice the amount of cold energy released by an ordinary fin-tube-type heat exchanger even if the air velocity in the heat exchanger is reduced to about 0.38 times that of the fin-tube-type heat exchanger.},
doi = {},
journal = {},
number = ,
volume = ,
place = {United States},
year = {Thu Dec 31 00:00:00 EST 1998},
month = {Thu Dec 31 00:00:00 EST 1998}
}

Conference:
Other availability
Please see Document Availability for additional information on obtaining the full-text document. Library patrons may search WorldCat to identify libraries that hold this conference proceeding.

Save / Share:
  • This paper presents a comparison of experimental data with a recently published model of heat exchange in irrigated packed beds. Heat transfer and pressure drop were measured in a 150 mm (ID) column with a 610-mm bed of metal Pall rings. Molten nitrate salt and preheated air were the working fluids with a salt inlet temperature of approximately 440/degree/C and air inlet temperatures of approximately 230/degree/C. A comparison between the experimental data and the heat transfer model is made on the basis of heat transfer from the salt. For the range of air and salt flow rates tested, 0.3 tomore » 1.2 kg/m/sup 2/ s air flow and 6 to 18 kg/m/sup 2/ s salt flow, the data agree with the model within 22% standard deviation. In addition, a model for the column pressure drop was validated, agreeing with the experimental data within 18% standard deviation over the range of column pressure drop from 40 to 1250 Pa/m. 25 refs., 7 figs., 2 tabs.« less
  • A low boiling water immiscible fluid containing two or more molecular species and having a variable boiling point is contacted in the liquid state with relatively hot or warm water such as surface sea water or geothermal water, thereby generating vapor of immiscible fluid (together with a certain amount of water vapor) which is used to drive a prime mover such as a gas turbine and thereby produce mechanical energy; the exhaust vapor from the prime mover is condensed by direct contact with a relatively cool or cold liquid aqueous phase such as deep sea water or water from amore » lake or stream or cooling tower to condense the vapor; and the condensate is recycled. Provision is made for ridding water discharged from the system of entrained and dissolved immiscible fluid. By countercurrent flow of the liquid phases and by suitable matching techniques greater efficiency is obtained. The invention is also applicable to heat pumps.« less
  • The advantages of direct contact heat transfer over heat transfer utilizing conventional metallic heat exchangers are listed. The performance characteristics of a three-phase direct contact heat exchanger in near counterflow operation were evaluated using water as the continuous phase fluid and refrigerant 113 as the dispersed phase fluid. Conclusions are drawn from the results having to do with refrigerant injection technique, vessel operating height, mass flow rate of refrigerant, water inlet temperature, operation at pinch point temperature differences below 13 to 20/sup 0/C, and operation with a dispersed phase fluid less dense than water. (MHR)
  • This paper presents a comparison of experimental data with a recently published model of heat exchange in irrigated packed beds. Heat transfer and pressure drop were measured in a 150 mm (ID) column with a 610-mm bed of metal Pall rings. Molten nitrate salt and preheated air were the working fluids with a salt inlet temperature of approximately 440{degree}C and air inlet temperatures of approximately 230{degree}C. A comparison between the experimental data and the heat transfer model is made on the basis of heat transfer from the salt. For the range of air and salt flow rates tested, 0.3 tomore » 1.2 kg/m{sup 2} s air flow and 6 to 18 kg/m{sup 2} s salt flow, the data agree with the model within 22% standard deviation. In addition, a model for the column pressure drop was validated, agreeing with the experimental data within 18% standard deviation over the range of column pressure drop from 40 to 1250 Pa/m. 25 refs., 7 figs., 2 tabs.« less
  • A direct-contact heat exchanger has been investigated experimentally in order to obtain data to design a heat exchanger to utilize the energy supplied by a solar pond effectively. During the laboratory tests heat transfer coefficients of 40 kW/m/sup 3/K were achieved at low temperature differentials. The heat was transferred from a 20% weight NaCl-solution to a number of different thermal oils and the results indicated that the heat transfer coefficients are primarily a function of the flow characteristics within the heat exchanger column and not of the physical or the thermal properties of the fluid.