skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: Solar heating and hot water system installed at Listerhill, Alabama

Abstract

The solar system was installed into a new buildng and was designed to provide 79% of the estimated annual space heating load and 59% of the estimated annual potable hot water requirement. The collectors are flat plate, liquid manufactured by Reynolds Metals Company and cover a total area of 2344 square feet. The storage medium is water inhibited with NALCO 2755 and the container is an underground, unpressurized steel tank with a capacity of 5000 gallons. This final report describes in considerable detail the solar heating facility and contains detailed drawings of the completed system.

Publication Date:
Research Org.:
Reynolds Metals Co., Richmond, VA (USA)
OSTI Identifier:
6351546
Report Number(s):
DOE/NASA/CR-150870
DOE Contract Number:
G-77-A-01-4070
Resource Type:
Technical Report
Country of Publication:
United States
Language:
English
Subject:
14 SOLAR ENERGY; INDUSTRIAL PLANTS; SOLAR HEATING SYSTEMS; SOLAR WATER HEATERS; DESIGN; ALABAMA; FLAT PLATE COLLECTORS; INSTALLATION; SENSIBLE HEAT STORAGE; THERMAL EFFICIENCY; WATER; APPLIANCES; EFFICIENCY; ELECTRIC APPLIANCES; ENERGY STORAGE; GAS APPLIANCES; HEAT STORAGE; HEATERS; HEATING SYSTEMS; HYDROGEN COMPOUNDS; NORTH AMERICA; OXYGEN COMPOUNDS; SOLAR COLLECTORS; SOUTHEAST REGION; STORAGE; USA; WATER HEATERS; 140901* - Solar Thermal Utilization- Space Heating & Cooling; 140907 - Solar Thermal Utilization- Water Heating

Citation Formats

Not Available. Solar heating and hot water system installed at Listerhill, Alabama. United States: N. p., 1978. Web. doi:10.2172/6351546.
Not Available. Solar heating and hot water system installed at Listerhill, Alabama. United States. doi:10.2172/6351546.
Not Available. Fri . "Solar heating and hot water system installed at Listerhill, Alabama". United States. doi:10.2172/6351546. https://www.osti.gov/servlets/purl/6351546.
@article{osti_6351546,
title = {Solar heating and hot water system installed at Listerhill, Alabama},
author = {Not Available},
abstractNote = {The solar system was installed into a new buildng and was designed to provide 79% of the estimated annual space heating load and 59% of the estimated annual potable hot water requirement. The collectors are flat plate, liquid manufactured by Reynolds Metals Company and cover a total area of 2344 square feet. The storage medium is water inhibited with NALCO 2755 and the container is an underground, unpressurized steel tank with a capacity of 5000 gallons. This final report describes in considerable detail the solar heating facility and contains detailed drawings of the completed system.},
doi = {10.2172/6351546},
journal = {},
number = ,
volume = ,
place = {United States},
year = {Fri Dec 01 00:00:00 EST 1978},
month = {Fri Dec 01 00:00:00 EST 1978}
}

Technical Report:

Save / Share:
  • Information is provided on the solar energy system installed at the Huntsville Senior Citizen Center. The solar space heating and hot water facility and the project involved in its construction are described in considerable detail and detailed drawings of the complete system and discussions of the planning, the hardware, recommendations, and other pertinent information are included. The facility was designed to provide 85 percent of the hot water and 85 percent of the space heating requirements. Two important factors concerning this project for commercial demonstration are the successful use of silicon oil as a heat transfer fluid and the architecturallymore » aesthetic impact of a large solar energy system as a visual centerpoint. There is no overheat or freeze protection due to the characteristics of the silicon oil and the design of the system. Construction proceeded on schedule with no cost overruns. It is designed to be relatively free of scheduled maintenance, and has experienced practically no problems.« less
  • This final report describes the solar energy hot water system installed at LaQuinta Motor Inn Inc., at Mobile, Alabama. The building is a 122 unit motel. The system consists of six rows of ten collectors and three rows of eleven collectors (1990 square feet) mounted on the roof. Griswald flow control valves were installed to regulate the flow to each row. Two Heliotrope electronic thermometers with a combined capability of measuring the temperatures of 22 different locations were installed for monitoring purposes. Engineering drawings, component specifications, and operator instructions are included.
  • This document is the Final Report of the Solar Energy System Installed at the First Solar Heated Office Building, One Solar Place, Dallas, Texas. The Solar System was designed to provide 87 percent of the space heating needs, 100 percent of the potable hot water needs and is sized for future absorption cooling. The collection subsystem consists of 28 Solargenics, series 76, flat plate collectors with a total area of 1596 square feet. The solar loop circulates an ethylene glycol-water solution through the collectors into a hot water system heat exchanger. The hot water storage subsystem consists of a heatmore » exchanger, two 2300 gallon concrete hot water storage tanks with built in heat exchangers and a back-up electric boiler. The domestic hot water subsystem sends hot water to the 10,200 square feet floor area office building hot water fixtures. The building cold water system provides make-up to the solar loop, the heating loop, and the hot water concrete storage tanks. The design, construction, cost analysis, operation and maintenance of the solar system are described. The system became operational July 11, 1979.« less
  • The Solar Energy System located at the Columbia Gas Corporation, Columbus, Ohio, has 2978 ft/sup 2/ of Honeywell single axis tracking, concentrating collectors and provides solar energy for space heating, space cooling and domestic hot water. A 1,200,000 Btu/h Bryan water-tube gas boiler provides hot water for space heating. Space cooling is provided by a 100 ton Arkla hot water fired absorption chiller. Domestic hot water heating is provided by a 50 gallon natural gas domestic storage water heater. Extracts are included from the site files, specification references, drawings, installation, operation and maintenance instructions.
  • The building has approximately 5600 square feet of conditioned space. Solar energy is used for space heating, space cooling, and preheating domestic hot water (DHW). The solar energy system has an array of evacuated tube-type collectors with an area of 1068 square feet. A 50/50 solution of ethylene glycol and water is the transfer medium that delivers solar energy to a tube-in-shell heat exchanger that in turn delivers solar-heated water to a 1100 gallon pressurized hot water storage tank. When solar energy is insufficient to satisfy the space heating and/or cooling demand, a natural gas-fired boiler provides auxiliary energy tomore » the fan coil loops and/or the absorption chillers. Extracts from the site files, specification references, drawings, and installation, operation and maintenance instructions are included.« less