Performance of electronic ballasts and other new lighting equipment. Final report
This study discusses parameters for selecting the most suitable auxiliary lighting device to operate and control gas-discharge lamps. The devices tested in this study include solid-state fluorescent and high-intensity discharge (HID) ballasts; current limiters; and dynamic lighting controls. They have been evaluated in combination with the standard 40-W, F-40, T-12, rapid-start, cool-white fluorescent lamps. Solid-state ballast performance varied widely- from 68 to 79 lumens per watt (lm/W) in efficacy and from 0.83 to 0.98 in ballast factor. System efficacy was up to 26% higher than standard core-coil ballast efficacy. Current limiters used with standard core-coil ballast reduce light output and input power by 30 to 50% and may be suitable as retrofit devices to reduce light in overilluminated spaces. When operated at a constant lamp wall temperature, these devices either maintain or reduce system efficacy.