Title: Moisture measurements in residential attics containing radiant barriers

Abstract

Tests were conducted by Oak Ridge National Laboratory researchers at three unoccupied research houses in Karns, Tennessee, to determine the effects of moisture condensation on the underside of perforated horizontal radiant barriers during the winter of 1987--88. An experimental plan called for the houses to be operated at high indoor relative humidities (45 and 55% at 70{degree}F), with data concerning the attic moisture conditions collected by both visual and instrument measurements. The testing showed that moisture went through a diurnal cycle. Moisture could condense on the bottom surface of a horizontal barrier in cold (below 35{degree}F) weather, but it could also dissipate to the attic air during a normal Tennessee winter afternoon, leaving the barrier dry. In long periods of subfreezing weather, all the condensation did not vaporize, as some remained on the surface through the day. However, the testing did show that the moisture cycle occurring on a perforated horizontal radiant barrier during a typical Tennessee winter did not appear to pose any structural, wet insulation, or stained ceiling problems to the Karns research houses, even though they were operated at higher than normal indoor relative humidities. Care should be taken in extrapolating the observations of this experimental workmore » to areas with prolonged periods of subfreezing weather. The diurnal moisture cycle under a barrier may be different in colder climates. Further testing of horizontal barriers in colder climates is recommended. 21 refs., 44 figs., 11 tabs.« less

Authors:
; ;  [1]
  1. Oak Ridge National Lab., TN (USA)
Publication Date:
Research Org.:
Electric Power Research Inst., Palo Alto, CA (USA); Oak Ridge National Lab., TN (USA)
Sponsoring Org.:
EPRI
OSTI Identifier:
5737521
Report Number(s):
EPRI-CU-6495
DOE Contract Number:  
AC05-84OR21400
Resource Type:
Technical Report
Country of Publication:
United States
Language:
English
Subject:
32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATION; ATTICS; MOISTURE; MEASURING METHODS; HEAT TRANSFER; HUMIDITY; PERFORMANCE TESTING; PROGRESS REPORT; RESIDENTIAL BUILDINGS; THERMAL BARRIERS; THERMAL INSULATION; BUILDINGS; DOCUMENT TYPES; ENERGY TRANSFER; TESTING; 320107* - Energy Conservation, Consumption, & Utilization- Building Systems- (1987-)

Citation Formats

Levins, W P, Karnitz, M A, Hall, J A, and Tennessee Valley Authority, Knoxville, TN. Moisture measurements in residential attics containing radiant barriers. United States: N. p., 1989. Web.
Levins, W P, Karnitz, M A, Hall, J A, & Tennessee Valley Authority, Knoxville, TN. Moisture measurements in residential attics containing radiant barriers. United States.
Levins, W P, Karnitz, M A, Hall, J A, and Tennessee Valley Authority, Knoxville, TN. Tue . "Moisture measurements in residential attics containing radiant barriers". United States.
@article{osti_5737521,
title = {Moisture measurements in residential attics containing radiant barriers},
author = {Levins, W P and Karnitz, M A and Hall, J A and Tennessee Valley Authority, Knoxville, TN},
abstractNote = {Tests were conducted by Oak Ridge National Laboratory researchers at three unoccupied research houses in Karns, Tennessee, to determine the effects of moisture condensation on the underside of perforated horizontal radiant barriers during the winter of 1987--88. An experimental plan called for the houses to be operated at high indoor relative humidities (45 and 55% at 70{degree}F), with data concerning the attic moisture conditions collected by both visual and instrument measurements. The testing showed that moisture went through a diurnal cycle. Moisture could condense on the bottom surface of a horizontal barrier in cold (below 35{degree}F) weather, but it could also dissipate to the attic air during a normal Tennessee winter afternoon, leaving the barrier dry. In long periods of subfreezing weather, all the condensation did not vaporize, as some remained on the surface through the day. However, the testing did show that the moisture cycle occurring on a perforated horizontal radiant barrier during a typical Tennessee winter did not appear to pose any structural, wet insulation, or stained ceiling problems to the Karns research houses, even though they were operated at higher than normal indoor relative humidities. Care should be taken in extrapolating the observations of this experimental work to areas with prolonged periods of subfreezing weather. The diurnal moisture cycle under a barrier may be different in colder climates. Further testing of horizontal barriers in colder climates is recommended. 21 refs., 44 figs., 11 tabs.},
doi = {},
journal = {},
number = ,
volume = ,
place = {United States},
year = {1989},
month = {8}
}

Technical Report:
Other availability
Please see Document Availability for additional information on obtaining the full-text document. Library patrons may search WorldCat to identify libraries that may hold this item. Keep in mind that many technical reports are not cataloged in WorldCat.

Save / Share: