Title: Hazard-evaluation and technical-assistance report HETA 90-122-l2073, technical assistance to San Francisco General Hospital and Medical Center, San Francisco, California

Abstract

In response to a request from the Director of the Environmental Health and Safety Department of the San Francisco General Hospital and Medical Center, located in San Francisco, California, an evaluation was undertaken of possible hazardous working conditions at that site. Concern existed about exposures to hazards while operating the germicidal lamp at the facility. Germicidal lamps were used to disinfect the air in tuberculosis and aerosolized pentamidine clinics. The workers wore no protective eye wear. All rooms used a 30 watt germicidal lamp. Lower wattage bulbs in the smaller rooms would have reduced occupational ultraviolet (UV) exposure. Reflectance levels of UV radiation were quite high and varied. Worker exposure to germicidal lamp UV levels was dependent on many factors, some of the most important ones being the position of the bulb in the room, age of the bulb, obstruction of the UV radiation by objects near the bulb, and the height of the worker. While there are no consensus guidelines available on ventilation systems designed for areas where germicidal lamps are used, the provision of good room air distribution and mixing is recommended to prevent stagnant air conditions or short circuiting of supply air within the room. Bulb changersmore » need to be aware of the need for protective clothing and gloves for protection from both the UV radiation levels as well as possible glass breakage.« less

Authors:
;
Publication Date:
Research Org.:
National Inst. for Occupational Safety and Health, Cincinnati, OH (USA)
OSTI Identifier:
5612639
Report Number(s):
PB-91-169359/XAB; HETA-90-122-L2073
Resource Type:
Technical Report
Country of Publication:
United States
Language:
English
Subject:
99 GENERAL AND MISCELLANEOUS//MATHEMATICS, COMPUTING, AND INFORMATION SCIENCE; HOSPITALS; ULTRAVIOLET RADIATION; OCCUPATIONAL EXPOSURE; RISK ASSESSMENT; VENTILATION; BUILDINGS; ELECTROMAGNETIC RADIATION; MEDICAL ESTABLISHMENTS; RADIATIONS; 552000* - Public Health

Citation Formats

Moss, C E, and Seitz, T. Hazard-evaluation and technical-assistance report HETA 90-122-l2073, technical assistance to San Francisco General Hospital and Medical Center, San Francisco, California. United States: N. p., 1990. Web.
Moss, C E, & Seitz, T. Hazard-evaluation and technical-assistance report HETA 90-122-l2073, technical assistance to San Francisco General Hospital and Medical Center, San Francisco, California. United States.
Moss, C E, and Seitz, T. 1990. "Hazard-evaluation and technical-assistance report HETA 90-122-l2073, technical assistance to San Francisco General Hospital and Medical Center, San Francisco, California". United States.
@article{osti_5612639,
title = {Hazard-evaluation and technical-assistance report HETA 90-122-l2073, technical assistance to San Francisco General Hospital and Medical Center, San Francisco, California},
author = {Moss, C E and Seitz, T},
abstractNote = {In response to a request from the Director of the Environmental Health and Safety Department of the San Francisco General Hospital and Medical Center, located in San Francisco, California, an evaluation was undertaken of possible hazardous working conditions at that site. Concern existed about exposures to hazards while operating the germicidal lamp at the facility. Germicidal lamps were used to disinfect the air in tuberculosis and aerosolized pentamidine clinics. The workers wore no protective eye wear. All rooms used a 30 watt germicidal lamp. Lower wattage bulbs in the smaller rooms would have reduced occupational ultraviolet (UV) exposure. Reflectance levels of UV radiation were quite high and varied. Worker exposure to germicidal lamp UV levels was dependent on many factors, some of the most important ones being the position of the bulb in the room, age of the bulb, obstruction of the UV radiation by objects near the bulb, and the height of the worker. While there are no consensus guidelines available on ventilation systems designed for areas where germicidal lamps are used, the provision of good room air distribution and mixing is recommended to prevent stagnant air conditions or short circuiting of supply air within the room. Bulb changers need to be aware of the need for protective clothing and gloves for protection from both the UV radiation levels as well as possible glass breakage.},
doi = {},
url = {https://www.osti.gov/biblio/5612639}, journal = {},
number = ,
volume = ,
place = {United States},
year = {Mon Oct 01 00:00:00 EDT 1990},
month = {Mon Oct 01 00:00:00 EDT 1990}
}

Technical Report:
Other availability
Please see Document Availability for additional information on obtaining the full-text document. Library patrons may search WorldCat to identify libraries that may hold this item. Keep in mind that many technical reports are not cataloged in WorldCat.

Save / Share: