Title: 1200-kV system study

Abstract

The 1200kV Systems Study Project consisted of two major tasks: definition of performance requirements for a 1200kV circuit breaker for use in a gas-insulated substation; and performance analysis of a 1200 kV insolator/disconnect switch for gas-insulated substation. For the first task, the performance requirements included: insulation requirements - 60 Hz, switching surge and lightning, both phase to ground and across the open breaker; prospective transient recovery voltage requirements related to fault current interrupting; an opening scheme capable of limiting phase to ground and across the breaker overvoltages resulting from line dropping and out of phase switching; a closing scheme capable of limiting line overvoltages during reclosing to 1.5 pu (2 percent level). The investigation of each of these items and of lightning characteristics and effects is discussed. The 1200 kV disconnect switch study analyzed bus energizing, bus de-energizing, transformer de-energizing, and the effect of hysteresis losses. Results from these analyses are presented. (LCL)

Publication Date:
Research Org.:
Brown Boveri Electric, Inc., Chalfont, PA (USA)
OSTI Identifier:
5459811
Report Number(s):
DOE/ET/29064-1
ON: DE82014512
DOE Contract Number:  
AC01-78ET29064
Resource Type:
Technical Report
Resource Relation:
Other Information: Portions of document are illegible
Country of Publication:
United States
Language:
English
Subject:
24 POWER TRANSMISSION AND DISTRIBUTION; CIRCUIT BREAKERS; PERFORMANCE; SPECIFICATIONS; GAS-INSULATED SUBSTATIONS; SWITCHES; OVERVOLTAGE; CONTROL; UHV AC SYSTEMS; ELECTRICAL INSULATION; FAILURES; LIGHTNING; SURGES; AC SYSTEMS; ELECTRIC DISCHARGES; ELECTRICAL EQUIPMENT; ENERGY SYSTEMS; EQUIPMENT; EQUIPMENT PROTECTION DEVICES; POWER SUBSTATIONS; POWER SYSTEMS; 200301* - Power Transmission & Distribution- AC Systems, EHV & UHV- (-1989)

Citation Formats

. 1200-kV system study. United States: N. p., 1982. Web.
. 1200-kV system study. United States.
. Mon . "1200-kV system study". United States.
@article{osti_5459811,
title = {1200-kV system study},
author = {},
abstractNote = {The 1200kV Systems Study Project consisted of two major tasks: definition of performance requirements for a 1200kV circuit breaker for use in a gas-insulated substation; and performance analysis of a 1200 kV insolator/disconnect switch for gas-insulated substation. For the first task, the performance requirements included: insulation requirements - 60 Hz, switching surge and lightning, both phase to ground and across the open breaker; prospective transient recovery voltage requirements related to fault current interrupting; an opening scheme capable of limiting phase to ground and across the breaker overvoltages resulting from line dropping and out of phase switching; a closing scheme capable of limiting line overvoltages during reclosing to 1.5 pu (2 percent level). The investigation of each of these items and of lightning characteristics and effects is discussed. The 1200 kV disconnect switch study analyzed bus energizing, bus de-energizing, transformer de-energizing, and the effect of hysteresis losses. Results from these analyses are presented. (LCL)},
doi = {},
journal = {},
number = ,
volume = ,
place = {United States},
year = {1982},
month = {2}
}

Technical Report:
Other availability
Please see Document Availability for additional information on obtaining the full-text document. Library patrons may search WorldCat to identify libraries that may hold this item. Keep in mind that many technical reports are not cataloged in WorldCat.

Save / Share: