Controlled closing on shunt reactor compensated transmission lines. Part 2: Application of closing control device for high-speed autoreclosing on BC Hydro 500 kV transmission line
Journal Article
·
· IEEE Transactions on Power Delivery
- Univ. of Technology, Vienna (Austria)
In the past, BC Hydro used circuit breaker closing resistors to limit switching surges on its 500 kV transmission system. This approach was considered undesirable for new transmission lines and an innovative scheme incorporating special transmission line surge arresters and controlled high speed autoreclosing of the circuit breaker was developed. The scheme and its basis as applied on a new 330 km long 500 kV transmission line are described. Actual line switching tests, also described, confirmed the validity of the studies performed and applied design concepts, and the value of the scheme.
- OSTI ID:
- 492192
- Report Number(s):
- CONF-960725-; ISSN 0885-8977; TRN: IM9730%%71
- Journal Information:
- IEEE Transactions on Power Delivery, Vol. 12, Issue 2; Conference: 1996 Summer meeting of the IEEE Power Engineering Society, Denver, CO (United States), 28 Jul - 1 Aug 1996; Other Information: PBD: Apr 1997
- Country of Publication:
- United States
- Language:
- English
Similar Records
Study and field verification of the effects of removing closing resistors from 500 kV circuit breakers
Composite membranes for fluid separations
Design studies for the Mead-Phoenix 500 kV AC transmission project
Conference
·
Wed Jan 01 00:00:00 EST 1992
· Proceedings of the American Power Conference; (United States)
·
OSTI ID:492192
+1 more
Composite membranes for fluid separations
Patent
·
Tue Feb 05 00:00:00 EST 1991
·
OSTI ID:492192
+1 more
Design studies for the Mead-Phoenix 500 kV AC transmission project
Journal Article
·
Sun Oct 01 00:00:00 EDT 1995
· IEEE Transactions on Power Delivery
·
OSTI ID:492192
+2 more