Title: Modeling the performance of small capacity lithium bromide-water absorption chiller operated by solar energy

Conference ·
OSTI ID:435583
 [1];  [2]
  1. Texas A and M Univ., College Station, TX (United States). Energy Systems Lab.
  2. Univ. of Technology, Baghdad (Iraq). Control and Systems Engineering Dept.

An analysis of the performance of a solar operated small capacity (two-ton) Lithium Bromide-Water (LiBr-H{sub 2}O) absorption system is conducted. The analysis is based on the first law of thermodynamics with lithium bromide as the absorbent and water as the refrigerant. The effect of various parameters affecting the machine coefficient of performance under various operating conditions is reported. Coefficient of performance of up to 0.8 can be obtained using flat plate solar collectors with generator temperatures in the range of 80--95 C (176--203 F). Liquid heat exchangers with effectiveness based on an NTU of the order of one would be a good design choice. The chiller can save approximately 3,456 kWh/yr per a two-ton unit, and it will reduce emissions by 19 lb of NO{sub x}, 5,870 lb of CO{sub 2}, and 16 lb of SO{sub x} per year per machine.

OSTI ID:
435583
Report Number(s):
CONF-960805-; TRN: IM9710%%241
Resource Relation:
Conference: 31. intersociety energy conversion engineering conference, Washington, DC (United States), 9-14 Aug 1996; Other Information: PBD: 1996; Related Information: Is Part Of Proceedings of the 31. intersociety energy conversion engineering conference. Volume 3: Policy impacts on energy, renewable energy resources, energy systems, environmental impact; Chetty, P.R.K.; Jackson, W.D.; Dicks, E.B. [eds.]; PB: 684 p.
Country of Publication:
United States
Language: